Please use this identifier to cite or link to this item: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/10456
Full metadata record
DC FieldValueLanguage
dc.creator.IDNOBRE, D. M.pt_BR
dc.creator.Latteshttp://lattes.cnpq.br/4154160480955578pt_BR
dc.contributor.advisor1SOUZA, Benemar Alencar de.-
dc.contributor.advisor1IDSOUZA, B. A.pt_BR
dc.contributor.advisor1Latteshttp://lattes.cnpq.br/4987294390789975pt_BR
dc.contributor.referee1CARVALHO JÚNIOR, Manoel Afonso de.-
dc.contributor.referee2NAIDU, Sreeramulu Raghuram.-
dc.description.resumoA forma de onda da tensão entre os terminais de disjuntores, quando da abertura de seus contatos, e definida como a tensão de restabelecimento e nos seus instantes iniciais como a tensão de restabelecimento transitória (TRT). Considerando a expansão dos sistemas de potencia, e possível que disjuntores de alta tensão não estejam mais adequados a interromper correntes de curto-circuito e suportar tensões transitórias. Neste trabalho e apresentado um estudo para a reavaliação dos disjuntores de 15 kV instalados na subestação Angelim, pertencente a Companhia Hidroelétrica do São Francisco (CHESF). E realizado um estudo para três disjuntores, obtendo formas de onda da TRT através de simulações digitais. E feita uma análise dos parâmetros da TRT, comparando-os com os valores estabelecidos em normas técnicas. Alternativas para a redução do pico e da taxa de crescimento da TRT sao propostas. A inserção de dispositivos de ZnO entre os terminais dos disjuntores produz redução significativa no pico da TRT.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.titleEstudo da adequabilidade de disjuntores de classe 15 kv às solicitações de TRT.pt_BR
dc.date.issued1999-11-09-
dc.description.abstractThe voltage transient that occurs across the terminals of a pole of a switching device upon interrupion of the current flowing through the pole is called Transient Recovery Voltage (TRY). Due to power system growth, it is possible that high voltage circuit breakers are not able to interrupt short-circuit currents, and to withstand the TRY. This is a study for the reevaluation of 15 kV breaker performances at Companhia Hidroeletrica do Sao Francisco (CHESF) Angelirn Substation. Digital simulations are carried out to compute the TRY parameters and to compare them with the standard ones. Alternatives are proposed to reduce the peaks and rate of rise of TRVs. It is shown that ZnO devices placed across the breaker terminals are very effective in reducing TRY peaks.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/10456-
dc.date.accessioned2019-12-24T11:26:00Z-
dc.date.available2019-12-24-
dc.date.available2019-12-24T11:26:00Z-
dc.typeDissertaçãopt_BR
dc.rightsAcesso Abertopt_BR
dc.creatorNOBRE, Diana Moreno.-
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeStudy of the suitability of class 15 kv circuit breakers to TRT requests.pt_BR
dc.identifier.citationNOBRE, Diana Moreno. Estudo da adequabilidade de disjuntores de classe 15 kv às solicitações de TRT. 1999. 101f. (Dissertação de Mestrado em Engenharia Elétrica), Curso de Pós-Graduação em Engenharia Elétrica, Centro de Ciências e Tecnologia, Universidade Federal da Paraíba – Campus II - Campina Grande - PB - Brasil, 1999.pt_BR
Appears in Collections:Mestrado em Engenharia Elétrica.

Files in This Item:
File Description SizeFormat 
DIANA MORENO NOBRE - DISSERTAÇÃO PPGEE 1999.pdfDiana Moreno Nobre - Dissertação PPGEE 19995.1 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.