Please use this identifier to cite or link to this item: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/11299
Title: Caracterização das perdas no sistema de abastecimento d'água do município de Queimadas-Paraíba.
Other Titles: Characterization of losses in the water supply system in the municipality of Queimadas-Paraíba.
???metadata.dc.creator???: OLIVEIRA JÚNIOR, José Lima de.
???metadata.dc.contributor.advisor1???: OLIVEIRA, Rui de.
???metadata.dc.contributor.referee1???: COURA, Mônica Amorim.
???metadata.dc.contributor.referee2???: ANDRADE NETO, Cícera Onofre de.
Keywords: Perdas de Águas - Queimadas -PB;Sistema de Abastecimento de Água;Escassez de Água;Vazamentos;Controle de Perdas;Hidrômetros;Rede de Distribuição;Water Losses - Queimadas -PB;Water Supply System;Water Shortage;Leaks;Loss Control;Hydrometers;Distribution Network
Issue Date: May-2005
Publisher: Universidade Federal de Campina Grande
Citation: OLIVEIRA JÚNIOR, José Lima de. Caracterização das perdas no sistema de abastecimento d'água do município de Queimadas-Paraíba. 2005. 124f. (Dissertação de Mestrado em Engenharia Civil e Ambiental), Programa de Pós-Graduação em Engenharia Civil e Ambiental, Universidade Federal de Campina Grande - Paraíba - Brasil, 2005. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/11299
???metadata.dc.description.resumo???: O presente trabalho caracterizou as perdas físicas e não físicas, do sistema de abastecimento de água da cidade de Queimadas, através de duas metodologias de estimativa de perdas, a da vazão minima noturna e a da estimativa das perdas aparentes aplicada pela EMBASA na região metropolitana de Salvador-BA. A cidade de Queimadas esta localizada no Cariri Paraibano (07° 22' 12" Sul e 35° 54' 30" Oeste), a 138 km da Capital, João Pessoa, e a 14 km ao sul de Campina Grande, com uma população de 36.032 habitantes (IBGE, 2000). Os dados das series históricas de volumes macromedidos e micromedidos foram obtidos pela CAGEPA e cobriram os meses de Janeiro a dezembro de 2003. Foram estabelecidos três setores de medição com 124, 424 e 299 ligações respectivamente, dentro da zona de pressão ZPR-1, abastecida pelo reservatório R-l e responsável por 78,53 % do total de ligações ativas do sistema. Nesses setores foram instalados medidores do tipo Woltmann, num período de três semanas, para o monitoramento da vazão minima noturna entre 3 e 4 horas da manha ao longo de um período de 6 dias, bem como registradores de pressão com gráfico circular para o monitoramento de 24 horas das pressões. O primeiro método estimativo consistiu em aplicar um Fator Noite-Dia (END) a vazão minima noturna encontrada nos setores de medição para obtenção da perda física diária nos setores. Os valores dos fatores Noite-Dia encontrados para os setores SMV-1, SMV-2 e SMV-3, mostraram-se dentro da faixa adequada para sistemas com caixas d'água domiciliares, usualmente inferiores a 24 horas As pressões na rede, nos três setores, atenderam a Norma Brasileira NBR - NM - 12218 da ABNT. Para a estimativa das perdas físicas e não físicas do sistema como um todo, foi computada a media das perdas diárias obtidas nos três setores de medição proporcionalmente ao numero total de ligações do sistema em cada mês do ano de 2003. O segundo método estimou, para cada mês do ano de 2003, as componentes das perdas aparentes através de dados operacionais estimados para o sistema, encontrando-se as perdas físicas pela diferença entre essas e o volume perdido mensal. O sistema apresentou condições físicas e de controle operacional precárias, o que requer adequação do sistema requerendo melhorias para uma estimativa mais acurada das perdas físicas e não físicas. O perfil de consumo da população mostrou-se predominantemente residencial representando 96,45 % do total de ligações. O índice de perda médio do sistema ficou em 38,78 % do volume total produzido. Já os índices de perdas físicas e aparentes estimados pelo método da vazão minima noturna foram, respectivamente, de 44,31 e 55,69 %, e pelo método da EMBASA, de 41,43 e 58,57 % respectivamente, demonstrando compatibilidade entre si. As perdas aparentes foram significativamente maiores que as perdas físicas, representando 33,16 % do faturamento anual da CAGEPA no sistema de Queimadas. As perdas totais representaram 59,55 % do faturamento anual da CAGEPA no sistema estudado.
Abstract: This work estimates the real and apparent water losses in the distribution system of the city of Queimadas, PB, using two methods of estimation. The city of Queimadas, PB, is located in the "Cariri" geographical region of the state. The city is located 138 kilometers from the state capital of Joao Pessoa and 14 kilometers south of the city of Campina Grande. The city has a population of about 36,032 inhabitants, according to the federal census taken in 2000. The historical data for the water system was supplied by CAGEPA. The data covers the year of 2003 January to December. Three different areas for measurement, described as "sectors", were established for study. The first with 124 (one hundred and twenty-four) users, the second with 424 (four hundred and twenty-four) users, and the last with 299 (two hundred and ninety nine) users connected to the ZPR-1 distribution zone, supplied by the R-l reservoir which Is responsible for 78.53 % of the distribution to the city. A Woltmann meter was installed to take measurements over three different weeks in order to monitor the minimum night flow from 3:00 AM to 4:00 AM over a period of six days, as well as a measurement of line pressure using a paper disc registration device which registered the pressure in each sector over a 24 (Twenty-four) hour period within three distinct and separate weeks. The first method used for arriving at the estimates consisted of applying a NDF (Night-Day Factor) to the minimum night flow data collected In each sector in order to estimate the real treated water loss. The results for NDF fit within the expected range for systems, that provide water for homes with home water storage systems, which is 24 hours or less. The pressure measurements was within the range prescribed by the Technical Norm NBR - NM - 12218 of the ABNT In order to arrive at an estimate of the real and apparent water losses from the distribution system as a whole, computations were made of the average of the daily losses from the three sectors proportionally to the total number of connections of the system in each month of the year. The second method of estimation used formulas in which parameters obtained from figures available in specialized publications were used in order to estimate the apparent loss, calculating the real loss for each month of 2003, against total lost water volume. The distribution system studied demonstrated precarious conditions in both its physical state and its operational control, which will require improvements In order to, more accurately, estimate real and apparent treated water loss in the future. Residential usage represents 96.45 % of the connections within the distribution system. The average loss index for the system Is about 38.78 % of the total volume of treated water produced for the system. The index for loss using the night flow data method was 44.31 % and 55.69 % respectively, while the estimate arrived at using the EMBASA's method was 41.43 % and 58.57 % respectively, demonstrating the compatibility of the two methods applied. The apparent losses were significantly higher that the real losses. The total volume of treated water lost from the system represented a revenue loss of 59.55 % when compared to annual income figures for 2003 published by the treated water providor, CAGEPA In the system of Queimadas.
Keywords: Perdas de Águas - Queimadas -PB
Sistema de Abastecimento de Água
Escassez de Água
Vazamentos
Controle de Perdas
Hidrômetros
Rede de Distribuição
Water Losses - Queimadas -PB
Water Supply System
Water Shortage
Leaks
Loss Control
Hydrometers
Distribution Network
URI: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/11299
Appears in Collections:Mestrado em Engenharia Civil e Ambiental.

Files in This Item:
File Description SizeFormat 
JOSÉ LIMA DE OLIVEIRA JÚNIOR - DISSERTAÇÃO PPGECA 2005.pdfJosé Lima de Oliveira Júnior - Dissertação PPGECA 2005.12.7 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.