Title: | Análise eletrotérmica de um transformador de potência. |
Other Titles: | Electrothermal analysis of a power transformer. |
???metadata.dc.creator???: | ALVES, Helem Monyelle de Mélo. |
???metadata.dc.contributor.advisor1???: | COSTA, Edson Guedes da. |
???metadata.dc.contributor.referee1???: | OLIVEIRA NETO, Antônio Barbosa de. |
Keywords: | Análise eletrotérmica;Transformador de potência;Curvas de hot-spot;Temperatura de topo de óleo;Resposta térmica de transformadores de potência;Matlab;Electrothermal analysis;Power transformer;Hot-spot curves;Oil top temperature;Thermal response of power transformers |
Issue Date: | 27-Jul-2017 |
Publisher: | Universidade Federal de Campina Grande |
Citation: | ALVES, Helem Monyelle de Mélo. Análise eletrotérmica de um transformador de potência. 2017. 47f. (Trabalho de Conclusão de Curso - Monografia), Curso de Bacharelado em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba - Brasil, 2017. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/18770 |
???metadata.dc.description.resumo???: | Neste trabalho, a resposta térmica de transformadores de potência foi avaliada por meio da análise de curvas da temperatura de hot-spot e da temperatura de topo de óleo. As curvas de temperatura foram obtidas a partir das especificações contidas na norma IEC 60076-7. De posse dos dados, uma análise de sensibilidade foi realizada para três estudos de caso. O Estudo de Caso 1 consistiu na avaliação do comportamento térmico do transformador diante de condições normais de carga; no Estudo de Caso 2 foi simulada uma condição de sobrecarga de 120% por quatro horas e, no Estudo de Caso 3, uma sobrecarga de 140% por 30 minutos. Para a análise de sensibilidade foi escolhido variar os parâmetros do modelo térmico da IEC que tinham relação com as características de projeto do transformador. O software MATLAB® foi utilizado para a construção dos gráficos. Com os resultados obtidos das simulações foi possível definir quais parâmetros exercem maior influência no comportamento térmico do transformador e quantificar a influência da variação destes parâmetros. |
Abstract: | In this work, power transformers thermal response was evaluated through the analysis of hot-spot temperature and oil top temperature curves. The temperature curves were obtained from the specifications contained in the IEC 60076-7 standard. From the data, a sensitivity analysis was performed for three case studies. Case Study 1 consisted in evaluating the transformer thermal behavior in the presence of normal load conditions; in Case Study 2 an overload condition of 120% was simulated for four hours and in Case Study 3 an overload of 140% for 30 minutes. For the sensitivity analysis, it was chosen to vary the IEC thermal model parameters related to the transformer design characteristics. The MATLAB® software was used to plot the graphs. With the results obtained from the simulations it was possible to define which parameters exert a greater influence on the transformer thermal behavior and to quantify the influence of these parameters variation. |
Keywords: | Análise eletrotérmica Transformador de potência Curvas de hot-spot Temperatura de topo de óleo Resposta térmica de transformadores de potência Matlab Electrothermal analysis Power transformer Hot-spot curves Oil top temperature Thermal response of power transformers |
???metadata.dc.subject.cnpq???: | Engenharia Elétrica. |
URI: | http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/18770 |
Appears in Collections: | Curso de Bacharelado em Engenharia Elétrica - CEEI - Monografias |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
HELEM MONYELLE DE MELO ALVES - TCC ENG. ELÉTRICA 2017 (1).pdf | Helem Monyelle de Mélo Alves - TCC Eng. Elétrica 2014. | 648.65 kB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.