dc.description.resumoA medição de resistência dinâmica (MRD) é uma técnica de diagnóstico utilizada para aferir o grau de degradação dos contatos de disjuntores. A mesma se destaca por ser capaz de analisar tanto os contatos principais como os de arco. Neste trabalho é realizada uma análise da reprodutibilidade dos resultados de ensaios de MRD implementados com e sem redução da velocidade de abertura dos contatos, além de uma análise sobre a influência do nível de corrente de teste nos ensaios de MRD. Para avaliar a metodologia, uma comparação foi feita utilizando o coeficiente de determinação (R2) entre os resultados de MRD executadas com velocidade reduzida e com velocidade nominal. Para realização dos ensaios, adotou-se um sistema alternativo de medição, que consiste em um osciloscópio digital, uma bateria estacionária, sensores de tensão e corrente e resistores de cromo-alumínio-ferro. O sistema proposto permite a aplicação de uma corrente de teste de até 300 A. Para reduzir a velocidade de abertura dos contatos, foi desenvolvido um sistema composto por um redutor de velocidade acoplado a um motor assíncrono que, por sua vez, foi acionado por um inversor de frequência. A partir dos resultados obtidos com as amostras estudadas, verificou-se que: os resultados de MRD executadas com velocidade nominal de abertura dos contatos não se repetem em ensaios similares; ensaios de MRD executados em velocidade nominal e utilizando os níveis mínimos de corrente de teste indicados pelas normas IEC e ANSI são altamente afetados pela interferência de películas de óleo, gerando diagnósticos errôneos e/ou não confiáveis; ensaios de MRD realizados com velocidade reduzida de abertura dos contatos fornecem maior reprodutibilidade dos resultados; para ensaios de MRD realizados com velocidade reduzida, níveis maiores de corrente de teste ajudam a aumentar a reprodutibilidade dos resultados, no entanto, este efeito diminui a medida que a velocidade de abertura vai aumentando.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica.pt_BR
dc.titleEnsaios de resistência dinâmica em disjuntores: análise de sensibilidade da corrente e da velocidade de abertura dos contatos.pt_BR
dc.date.issued2015-06-23
dc.description.abstractThe dynamic resistance measurement (DRM) is a diagnostic technique used to assess the operative state of circuit breaker contacts, that stands out for being able to analyze both the main and arcing contacts. In this research, an analysis of the result reproducibility of DRM tests is presented, which was implemented with speed reduction of the contact opening process, as well as an analysis of the test current level influence on DRM results. To evaluate the methodology, a comparison was made using the coefficient of determination (R2) between the results of the DRM tests carried out with speed reduction and at rated speed. To perform the tests, an alternative system was adopted, which consists of a digital oscilloscope, a stationary battery, current and voltage sensors and resistors made of chrome aluminum iron. The proposed system allows the injection of a direct current up to 300 A. To achieve the speed reduction of the contact opening process, a speed reducer was coupled with an asynchronous motor, which was triggered by a frequency inverter. From the obtained results with the samples studied, it can be verified that: the results of DRM tests carried out with rated speed of contact opening do not repeat themselves on similar tests; DRM tests carried out with rated speed of contact opening and using the minimum levels of test current indicated by IEC and ANSI standards are highly affected by the interference of oil films, thus, providing masked and unreliable results; DRM tests carried out with reduced speed of contact opening provides results with better reproducibility; for DRM tests carried out with reduced speed of contact opening, higher levels of test current help to increase the result reproducibility, however, this effect is not as noticeable as the opening speed increases.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/19967
dc.date.accessioned2021-07-09T21:14:08Z
dc.date.available2021-07-09
dc.date.available2021-07-09T21:14:08Z
dc.typeDissertaçãopt_BR
dc.subjectDisjuntores - ensaios de resistênciapt_BR
dc.subjectEnsaios de resistência dinâmica - disjuntorespt_BR
dc.subjectSensibilidade da corrente - análisept_BR
dc.subjectVelocidade de abertura dos contatospt_BR
dc.subjectResistência dinâmicapt_BR
dc.subjectCorrente de testept_BR
dc.subjectDiagnóstico em disjuntorespt_BR
dc.subjectDisjuntores de alta tensãopt_BR
dc.subjectManutenção em disjuntorespt_BR
dc.subjectCâmaras de extinçãopt_BR
dc.subjectCâmaras de extinçãopt_BR
dc.subjectDynamic resistance tests - circuit breakerspt_BR
dc.subjectCurrent sensitivity - analysispt_BR
dc.subjectCurrent sensitivity - analysispt_BR
dc.subjectDynamic resistancept_BR
dc.subjectTest currentpt_BR
dc.subjectDiagnosis in circuit breakerspt_BR
dc.subjectHigh voltage circuit breakerspt_BR
dc.subjectMaintenance on circuit breakerspt_BR
dc.subjectExtinction chamberspt_BR
dc.rightsAcesso Abertopt_BR
dc.creatorOLIVEIRA, Adriano Costa de.
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeDynamic resistance tests on circuit breakers: analysis of current sensitivity and contact opening speed.pt_BR
dc.identifier.citationOLIVEIRA, Adriano Costa de. Ensaios de resistência dinâmica em disjuntores: análise de sensibilidade da corrente e da velocidade de abertura dos contatos. 2015. 77f. (Dissertação de Mestrado) Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2015. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/19967pt_BR
Appears in Collections:Mestrado em Engenharia Elétrica.

Files in This Item:
File Description SizeFormat 
ADRIANO COSTA DE OLIVEIRA - DISSERTAÇÃO PPGEE 2015.pdfAdriano Costa de Oliveira - Dissertação PPGEE 2015.1.3 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.