dc.description.resumoNos dias atuais a confiabilidade e a continuidade no fornecimento de energia elétrica são cada vez mais exigidos. Os para-raios tem uma importante função neste processo que é de proteger os demais equipamentos integrantes da rede elétrica de sobretensões atmosféricas e de manobra. Quando falham, normalmente provocam o desligamento de linhas de transmissão ou de transformadores, penalizando severamente a concessionária pela indisponibilidade ou por multas impostas pela agência reguladora. Como todo equipamento importante para o sistema elétrico, os para-raios necessitam de técnicas eficazes de monitoramento. Na literatura e na indústria podem ser encontradas diversas técnicas, procedimentos ou equipamentos destinados ao seu monitoramento. Todos os procedimentos ou equipamentos possuem suas limitações, vantagens e desvantagens, sejam elas técnicas, econômicas ou operacionais. Visando suplantar algumas das limitações existentes nas técnicas e procedimentos normalmente empregados no setor elétrico, encontrase proposto neste trabalho uma metodologia de análise da condição operacional de para-raios em campo, com base em medições da corrente de fuga total. Com esta metodologia pretende-se minimizar as dificuldades operacionais relacionadas às atividades de monitoramento, uma vez que será medida apenas a corrente de fuga total, diferentemente de técnicas e procedimentos usuais que requerem também a medição da tensão aplicada. Um banco de dados de correntes de fuga foi obtido com medições realizadas em 05 (cinco) subestações. As medições foram agrupadas por modelo/fabricante e tempo de operação dos para-raios. O instrumento de medição utilizado é composto de um amperímetro do tipo alicate e um osciloscópio digital portátil. O processo de medição em campo mostrou-se efetivo e prático devido à facilidade de manuseio do instrumento utilizado. Ensaios em laboratório foram realizados para avaliação da metodologia e dos instrumentos de medição. A partir da base de dados produzida, foi possível com emprego de técnicas de processamento de sinais e estatística, observar o comportamento gaussiano dos dados e o crescimento do valor médio da componente de 3ª harmônica da corrente total em função do tempo de operação, evidenciando, assim, a correlação entre a elevação da corrente de fuga e a diminuição da vida útil dos para-raios.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica.pt_BR
dc.titleMonitoramento de para-raios de óxido de zinco em campo.pt_BR
dc.date.issued2014-09-02-
dc.description.abstractNowadays the reliability and continuity in the electricity supply are increasingly required. The surge arresters has an important function in this process, which is to protect the other utility equipment against lightning and switching surges. When they fail, usually causing the shutdown of transmission lines or transformers, severely penalizing the power utility for the unavailability or regulator fines. As any important equipment for the electrical system, surge arresters need effective monitoring techniques. In the literature and industry several techniques, procedures or equipment for their monitoring can be found. All procedures or devices have their limitations, advantages and disadvantages, whether technical, economic or operational. Aiming to overcome some of the limitations in existing techniques and procedures commonly employed in the electrical industry, a methodology for analyzing the surge arrester operational condition based on measurements of total leakage current is proposed in this paper. With this methodology is intended to minimize operational difficulties associated with monitoring activities, since it will only measure the total leakage current unlike the usual techniques and procedures, which require the measurement of the applied voltage, too. A database of leakage currents with measurements performed in five (05) power substations was obtained. Measurements were grouped by arresters model/manufacturer and operation time. The measuring instrument used consists of a clamp type ammeter and a portable digital oscilloscope. The process of field measurement was effective and practical due to the ease of handling of the used instrument. Laboratory tests were performed to evaluate the methodology and measuring instruments. From the database produced, it was possible through the use of techniques of signal processing and statistical observe the Gaussian behavior of the data and the average increase of the 3rd harmonic component of the total current as a function of operating time, which highlights thus, the correlation between the increase of the leakage current and the decrease of the lifetime of the surge arrester.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/448-
dc.date.accessioned2018-04-21T14:21:51Z-
dc.date.available2018-04-21-
dc.date.available2018-04-21T14:21:51Z-
dc.typeDissertaçãopt_BR
dc.subjectPara-Raios de Óxido de Zincopt_BR
dc.subjectCorrente de Fuga Totalpt_BR
dc.subjectVida Útil dos Para-Raiospt_BR
dc.subjectComportamento Gaussiano dos Dadospt_BR
dc.subjectLifetime of the Surge Arresterpt_BR
dc.subjectLeakage Current Totalpt_BR
dc.subjectEngenharia Elétricapt_BR
dc.subjectZinc Oxide's Surge Arresterpt_BR
dc.rightsAcesso Abertopt_BR
dc.creatorLIMA JÚNIOR, Geraldo Bezerra.-
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeMonitoring of zinc oxide surge arresters in the field.pt_BR
dc.identifier.citationLIMA JÚNIOR, Geraldo Bezerra. Monitoramento de para-raios de óxido de zinco em campo. 2014. 108 f. (Dissertação de Mestrado em Engenharia Elétrica), Programa de Pós-graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2014.pt_BR