Please use this identifier to cite or link to this item:
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/492
Full metadata record
DC Field | Value | Language |
---|---|---|
dc.creator.Lattes | http://lattes.cnpq.br/7603022844978260 | pt_BR |
dc.contributor.advisor1 | COSTA, Edson Guedes da. | - |
dc.contributor.advisor1ID | COSTA, E. G. | pt_BR |
dc.contributor.advisor1Lattes | http://lattes.cnpq.br/3930289115658143 | pt_BR |
dc.contributor.advisor2 | PEREIRA, Helder Alves. | - |
dc.contributor.advisor2ID | PEREIRA, H. A. | pt_BR |
dc.contributor.advisor2Lattes | http://lattes.cnpq.br/7393937425520096 | pt_BR |
dc.contributor.referee1 | SERRES, Alexandre Jean René. | - |
dc.contributor.referee2 | LIRA, George Rossany Soares de. | - |
dc.contributor.referee3 | FREIRE, Raimundo Carlos Silvério. | - |
dc.description.resumo | Neste trabalho é realizada uma avaliação da resposta impulsiva de aterramento com haste concretada, considerando o efeito da ionização do solo. Para isso, o aterramento foi representado e simulado utilizando uma ferramenta computacional de simulação em três dimensões por meio do método dos elementos finitos. A representação computacional, bem como a validação da mesma, foi feita tomando-se como base dados experimentais apresentados na literatura. O fenômeno da ionização do solo foi implementado ponto a ponto, utilizando o equacionamento do modelo dinâmico de ionização do solo, possibilitando que aterramentos com diferentes formatos geométricos sejam avaliados. Avaliou-se a impedância transitória de uma haste concretada padronizada para solos com diferentes resistividades. Além disso, procedeu-se com uma análise da resposta impulsiva da haste concretada para diferentes parâmetros geométricos, a saber: raio do concreto envolvente, comprimento vertical da haste concretada, comprimento vertical do concreto envolvente e profundidade da haste concretada em relação ao nível do solo. Por fim, propõem-se limites práticos e sugestões de dimensões para a haste concretada, de forma que a reposta impulsiva seja otimizada. | pt_BR |
dc.publisher.country | Brasil | pt_BR |
dc.publisher.department | Centro de Engenharia Elétrica e Informática - CEEI | pt_BR |
dc.publisher.program | PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA | pt_BR |
dc.publisher.initials | UFCG | pt_BR |
dc.subject.cnpq | Ciências | pt_BR |
dc.subject.cnpq | Engenharia Elétrica | pt_BR |
dc.title | Análise de sistemas de aterramento com hastes concretadas submetidos a correntes impulsivas. | pt_BR |
dc.date.issued | 2017-03-30 | - |
dc.description.abstract | In this research, was performed an impulsive response evaluation of concrete encased groundings, considering de soil ionization effect. In order to achive this, the grouding was represented and simulated in three dimensions using a finite element method software. The computational representation and validation were performed using experimental data presented in the literature. The soil ionization effect was implemented in a point form, allowing evaluate groudings with different geometric formats. It was studied the transient impedance of a standard concrete encased rod placed in soils with different resistivity values. Furthermore, was performed a transient response analysis for different geometric parameters of the concrete encased rod, namely: the concrete radius, the vertical length of the concrete encased rod, the vertical length of the concrete encased rod, the surrounding concrete and the depth of the concrete encased rod in relation to the soil surface. Finally, practical limits and suggested dimensions for the concrete encased rod are proposed, in order to optimize the impulse response. | pt_BR |
dc.identifier.uri | http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/492 | - |
dc.date.accessioned | 2018-04-25T17:58:53Z | - |
dc.date.available | 2018-04-25 | - |
dc.date.available | 2018-04-25T17:58:53Z | - |
dc.type | Dissertação | pt_BR |
dc.subject | Aterramentos - Concreto | pt_BR |
dc.subject | Hastes Concretadas | pt_BR |
dc.subject | Impedância Transitória | pt_BR |
dc.subject | Impulso de Corrente | pt_BR |
dc.subject | Ionização do Solo | pt_BR |
dc.subject | Concrete Encased Grounding | pt_BR |
dc.subject | Current Impulse | pt_BR |
dc.subject | Soil Ionization | pt_BR |
dc.subject | Transient Impedance | pt_BR |
dc.rights | Acesso Aberto | pt_BR |
dc.creator | BEZERRA, Gabriel Vidal Negreiros. | - |
dc.publisher | Universidade Federal de Campina Grande | pt_BR |
dc.language | por | pt_BR |
dc.description.sponsorship | CNPq | pt_BR |
dc.identifier.citation | BEZERRA, G. V. N. Análise de sistemas de aterramento com hastes concretadas submetidos a correntes impulsivas. 2017. 110 f. Dissertação (Mestrado em Engenharia Elétrica) – Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande, Paraíba, Brasil, 2017. | pt_BR |