dc.description.resumoA tese aqui relatada é o resultado de uma pesquisa de doutorado relacionada com a prova do princípio de um novo tipo de sistema radiométrico aplicado a detecção e estimação de localização de fontes de descargas parciais. Medição de Descarga Parcial (DP) é uma técnica de monitoramento do isolamento de alta tensão estabelecida e usada para facilitar a detecção de falhas incipientes em equipamentos de alta tensão. Com base na grande importância do sistema de energia, é constante a pesquisa sobre a natureza e as características das fontes de DP. Um sistema radiométrico de monitoramento de descargas parciais de baixo custo (comparado ao item monitorado) é descrito para aplicação de monitoramento em tempo real do estado de conservação, gestão de ativos e otimização de operações no futuro Smart Grid. O sistema de monitoramento de DP proposto baseia-se numa nova abordagem para a localização de fontes de DP que utiliza proporções de energia removendo a necessidade de sincronização entre os sensores, melhorando assim sua escalabilidade. A exigência de alta taxa de amostragem é também evitada pelo uso de um detector de envoltória. Para a avaliação proposta de sinais de DP, várias medições foram realizadas utilizando uma antena diskcone e um sistema comercial baseado no padrão IEC 60270. Estas medições, aqui relatadas, sugerem com sucesso que as fontes de descargas parciais podem ser detectadas e localizadas por meio de medições radiométricas no espaço livre de apenas potência do sinal. As medições foram feitas em dois locais com protocolos de medição semelhantes por três grupos de pesquisa colaboradores. Um conjunto de medição é mais animador do que o outro, mas uma possível explicação para a heterogeneidade dos resultados é apresentado. Sugere-se que um sistema que monitora apenas potência podem formar a base de uma rede de sensores sem fio de baixo custo para o monitoramento de descargas parciais em subestação de energia elétricapt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica-
dc.titleLocalização de descargas parciais baseada em um método radiométrico - prova do princípio.pt_BR
dc.date.issued2014-05-27-
dc.description.abstractThe thesis reported here is the result of a PhD research related to the proof of principle of a new type of radiometric system applied to detection and location estimation of partial discharges sources. Partial Discharge (PD) measurement is an established high voltage insulation monitoring technique used to facilitate the detection of incipient faults in high voltage apparatus. Based on the great importance of the power system, is constant the research about the nature and characteristics of PD sources. A low-cost (compared to the monitored item), free-standing, radiometric, partial discharge monitoring system is described for application to real-time condition monitoring, asset management and operations optimization in the future smart grid. The proposed PD monitoring system is based on a novel approach to PD location which uses power ratios to obviates the need for synchronization between sensors thereby improving scalability. The high sampling rate requirement is also avoided by the use of an envelope detector. For the proposed evaluation of PD signals, several measurements were performed using a diskcone antenna and a commercial system based on the IEC 60270 standard. These measurements reported here suggests successfully that partial discharge sources might be detected and located using power-only free-space radiometric measurements. The measurements were made in two locations with similar measurement protocols by three collaborating research groups. One measurement set is more encouraging than the other but a likely explanation for the disparate nature of the results is offered. It is suggested that a system based on amplitude only measurements might form the basis of a low-cost wireless sensor network for monitoring partial discharge in electricity substation.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9386-
dc.date.accessioned2019-11-21T18:14:51Z-
dc.date.available2019-11-21-
dc.date.available2019-11-21T18:14:51Z-
dc.typeTesept_BR
dc.subjectSistema Radiométrico-
dc.subjectDescarga Parcial-
dc.subjectEnvoltória-
dc.subjectRazão de Energias-
dc.subjectAlta Tensão - Equipamentos-
dc.subjectDetecção de Falhas-
dc.subjectSubestação de Energia Elétrica-
dc.subjectRadiômetro-
dc.subjectProva do Princípio-
dc.subjectRadiometric System-
dc.subjectPartial Discharge-
dc.subjectWrap-
dc.subjectEnergy Ratio-
dc.subjectHigh Voltage - Equipment-
dc.subjectFault Detection-
dc.subjectElectricity Substation-
dc.subjectRadiometer-
dc.subjectProof of Principle-
dc.rightsAcesso Abertopt_BR
dc.creatorSOUZA NETO, José Maurício Ramos de.-
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeLocalization of partial discharges based on a principle-proof radiometric method.pt_BR
dc.identifier.citationSOUZA NETO, José Maurício Ramos de. Localização de descargas parciais baseada em um método radiométrico - prova do princípio. 2014. 162f. (Tese de Doutorado em Engenharia Elétrica), Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba Brasil, 2014.pt_BR