dc.description.resumoOs sistemas de distribuição de energia elétrica estão sujeitos a eventos intempestivos que podem levar à interrupção do fornecimento de energia. Num sistema de distribuição em alta tensão com característica predominantemente radial e sem opções de transferência de carga, um desligamento intempestivo pode atingir uma região de grandes proporções em relação à área de concessão. Isolado ou sanado o defeito provocador do desligamento, inicia-se o processo de recomposição do sistema, que consiste na execução de manobras para energização de linhas de distribuição, subestações e cargas, que pode demandar dezenas de operações em religadores, chaves e disjuntores, demandando um tempo considerável para normalização do sistema de distribuição de 69 kV. O objetivo desse trabalho é fazer a análise da energização de um circuito de tensão de 69 kV mostrando que é possível com a operação de apenas um único equipamento de disjunção fazer a energização do sistema com risco aceitável de violação dos limites de suportabilidade dos equipamentos. Assim reduzindo sensivelmente o número de operações e o tempo de manobra para recomposição. Para isso é apresentada uma metodologia de estudo de transitórios eletromagnéticos através de simulações digitais via ATP (Alternative Transiente Program), utilizando técnicas e ferramentas de análise de resposta em frequência, estudo estatístico de chaveamento de disjuntores e estudo determinístico no domínio do tempo. Identificando situações de maior severidade quanto à sobretensões em função do barramento observado, do carregamento e da presença de bancos de capacitores. Assim evidenciando que mesmos nas situações de maior severidade quanto a sobretensões, é factível de execução da manobra de energização do sistema com a operação de um único equipamento de disjunção, reduzindo sensivelmente o tempo necessário para o restabelecimento do sistema de distribuição de 69 kV.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica-
dc.titleAprimoramento do processo de recomposição de um sistema de distribuição de 69 kV.pt_BR
dc.date.issued2015-05-
dc.description.abstractThe distribution power systems are subject to untimely events that can lead to disruption of power supply. The distribution power system for high voltage with characteristic predominantly radial and without charge transfer options, an untimely shutdown can reach a region of great proportions in relation to the concession area. Isolated or repaired the defect which triggered off the shutdown begins the process of rebuilding the system, consisting of the maneuverings for power-distribution lines, substations and loads, which may require dozens of operations in reclosers, switches and circuit breakers, demanding considerable time to normalization of the 69 kV dsitribution power system. The aim of this study is to analyze the effects of the nergization within a large area of an electric power system through only one 69 kV high voltage circuit breaker unit, without violating withstand limits of the system equipments.Thus significantly reducing the system recovering time. For this purpose we present an electromagnetic transient study methodology through digital simulations via ATP (Alternative Transient Program), using techniques and analysis tools in frequency domain tools, statistical switching study of circuit breakers and deterministic study in the time domain. Identifying situations of greater severity as the surge to reflect the observed bar loading and the presence of capacitor banks. Thus showing that in these situations of greater severity as the surge, it is feasible for the implementation of power-handling system with the operation of a single equipment disjunction, significantly reducing the time required for the restoration of the 69 kV distribution system.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9459-
dc.date.accessioned2019-11-25T12:05:10Z-
dc.date.available2019-11-25-
dc.date.available2019-11-25T12:05:10Z-
dc.typeDissertaçãopt_BR
dc.subjectManobra de Recomposição-
dc.subjectAnálise no Domínio da Frequência-
dc.subjectSistema de Distribuição 69 kV-
dc.subjectSobretensão de Manobra-
dc.subjectTransitórios Eletromagnéticos-
dc.subjectSimulações Digitais-
dc.subjectResetting Maneuver-
dc.subjectFrequency Domain Analysis-
dc.subject69 kV Distribution System-
dc.subjectManeuver Overvoltage-
dc.subjectElectromagnetic Transients-
dc.subjectDigital Simulations-
dc.rightsAcesso Abertopt_BR
dc.creatorFONTES, Alessandro Viana.-
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeImprovement of the recomposition process of a 69 kV distribution system.pt_BR
dc.identifier.citationFONTES, Alessandro Viana. Aprimoramento do processo de recomposição de um sistema de distribuição de 69 kV. 2015. 112 f. (Dissertação) Mestrado em Engenharia Elétrica, Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Campina Grande - Paraíba - Brasil, 2015.pt_BR
Appears in Collections:Mestrado em Engenharia Elétrica.

Files in This Item:
File Description SizeFormat 
ALESSANDRO VIANA FONTES - DISSERTAÇÃO PPGEE 2015.pdfAlessandro Viana Fontes - Dissertação PPGEE 201514.96 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.