Please use this identifier to cite or link to this item: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9484
Full metadata record
DC FieldValueLanguage
dc.creator.IDANDRADE, F. L. M.pt_BR
dc.creator.Latteshttp://lattes.cnpq.br/5536282693167252pt_BR
dc.contributor.advisor1COSTA, Edson Guedes da.-
dc.contributor.advisor1IDCOSTA, E. G.pt_BR
dc.contributor.advisor1Latteshttp://lattes.cnpq.br/3930289115658143pt_BR
dc.contributor.referee1NEVES, Washington Luiz de Araújo.-
dc.contributor.referee2FERREIRA, Tarso Vilela.-
dc.contributor.referee3BRAGA FILHO, Edgar Roosevelt.-
dc.description.resumoExiste uma carência de metodologias e ferramentas robustas para se avaliar os efeitos dos esforços eletromecânicos decorrentes das elevadas correntes transitórias sobre os equipamentos. Assim, este trabalho tem como objetivo estudar os esforços eletromecânicos decorrentes das correntes de curto circuito nos enrolamentos de transformadores, além de analisar a proximidade de falha dos enrolamentos por meio da comparação de dois critérios de falha mecânica, o critério da máxima tensão e o critério de Von Mises. Os esforços foram estudados em dois transformadores, um monofásico de 75 MVA e outro trifásico de 180 MVA. A partir dos resultados obtidos, contatou-se que a modelagem baseada no método dos elementos finitos, em comparação à formulação analítica, é o método mais adequado para determinação das forças eletromagnéticas. Além disso, verificou-se que a representação gráfica, em 3D, dos enrolamentos dos transformadores é necessária para determinação correta dos esforços eletromecânicos, uma vez que a geometria influencia diretamente na determinação dos esforços. Por fim, constatou-se que o critério de Von Mises é mais adequado para avaliar a proximidade de falha mecânica dos enrolamentos, em razão de utilizar mais parâmetros para a tomada de decisão, tornando-o mais exato. Pelo exposto, e pelas comparações apresentadas para os transformadores estudados, conclui-se que as comparações realizadas e verificações obtidas nesta dissertação podem ser generalizadas para outros transformadores. Possibilitando, assim, uma análise mais adequada sobre os esforços eletromecânicos ocorrentes nos transformadores de potência.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica-
dc.titleAvaliação dos estresses mecânicos nos enrolamentos de transformadores.pt_BR
dc.date.issued2016-02-22-
dc.description.abstractThere is a lack of robust methodologies and tools to evaluate the effects of electromechanical efforts caused by high transient currents on transformers. Thus, this work aims to study electromechanical efforts caused by short-circuit currents through transformer windings, as well as to analyze the windings failure proximity by comparing two mechanical failure criteria: the maximum tension criterion and the Von Mises criterion. Mechanical efforts were studied for two cases, a single-phase 75 MVA transformer and a three-phase 180 MVA transformer. It was found that modeling based on the Finite Element Method, compared to analytical formulation, is the mors appropriate for determining electromagnetic forces in transformer. Furthermore, it was found that a 3D graphic representation of the transformer windings is necessary for a correct determination of electromechanical efforts, since the geometry directly influences the effort configuration. Finally, it was found that the Von Mises criterion is more appropriate to evaluate the windings failure proximity, since this criterion use more parameters for decision-making, which make it more accurate. It is concluded that the comparisons and verifications obtained in this work can be generalized to other transformers. Enabling a more appropriate analysis of electromechanical efforts that occur in large power transformers.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9484-
dc.date.accessioned2019-11-25T14:38:35Z-
dc.date.available2019-11-25-
dc.date.available2019-11-25T14:38:35Z-
dc.typeDissertaçãopt_BR
dc.subjectTransformadores de Corrente-
dc.subjectTransformadores - Enrolamento-
dc.subjectVon Mises-
dc.subjectEstresse Mecânico-
dc.subjectCurtoCircuito-
dc.subjectForças Eletromagnéticas-
dc.subjectCurrent Transformers-
dc.subjectWinding Transformers-
dc.subjectMechanical Stress-
dc.subjectShort Circuit-
dc.subjectElectromagnetic Forces-
dc.rightsAcesso Abertopt_BR
dc.creatorANDRADE, Filipe Lucena Medeiros de.-
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeEvaluation of mechanical stresses in transformer windings.pt_BR
dc.identifier.citationANDRADE, Filipe Lucena Medeiros de. Avaliação dos estresses mecânicos nos enrolamentos de transformadores. 2016. 68f. (Dissertação) Mestrado em Engenharia Elétrica, Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Campina Grande - Paraíba - Brasil, 2016.pt_BR
Appears in Collections:Mestrado em Engenharia Elétrica.

Files in This Item:
File Description SizeFormat 
FILIPE LUCENA MEDEIROS DE ANDRADE - DISSERTAÇÃO PPGEE 2016.pdfFilipe Lucena Medeiros de Andrade - Dissertação PPGEE 20161.79 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.