dc.description.resumoEste artigo propõe um método para alocar e dimensionar várias restrições de corrente condicionadores de linha de energia ativos (APLCs) em redes de distribuição de energia. A localização e O tamanho dos APLCs é ideal em relação à topologia de distribuição de energia, independentemente perfil de consumo de carga, desde que a demanda distribuída de energia não exceda a potência em cada um dos pontos de acoplamento comum (PCC). O problema de otimização é declarado em termos da distorção harmônica total (THD) e da harmônica individual distorção (IHD) observada em cada PCC e leva em consideração restrições como perdas de linha, corrente mínima de compensação e quantidade mínima de unidades APLC. o As restrições visam atender a requisitos específicos de qualidade de energia, como os prescritos no IEEE 519-1992. Os resultados da simulação são apresentados para demonstrar a viabilidade do abordagem proposta, bem como enfatizar suas características distintas em comparação com e métodos bem conhecidos. A análise de estabilidade garantiu que os pontos ideais sejam estáveis para a fonte de corrente controlada com base na detecção de tensão, sem considerar os elementos de potência variação. O controle APLCs opera para diminuir as restrições de THD e IHD que cooperam com um ao outro sem qualquer comunicação. Todos os estudos, localização, dimensionamento e controle, foram testado em uma plataforma em tempo real e provou ser viável.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica
dc.titleLocalização, dimensionamento e controle de compensadores ativos em redes de distribuição.pt_BR
dc.date.issued2014-07-10
dc.description.abstractThis paper proposes a method for allocating and sizing multiple current-constrained active power line conditioners (APLCs) in power distribution networks. The location and size of the APLCs are optimal with respect to the power distribution topology regardless the load consumption pro le as long as the distributed power demand does not exceed the power rating at each one of the points of common coupling (PCC). The optimization problem is stated in terms of the total harmonic distortion (THD) and the individual harmonic distortion (IHD) observed at each PCC and takes into account constrains like minimum line losses, minimum compensation current and minimum quantity of APLC units. The constraints aims at satisfying speci c power quality requirements like the ones prescribed in IEEE 519-1992. Simulation results are presented to demonstrate the feasibility of the proposed approach as well as to emphasize its distinct features in comparison with similar and well known methods. The stability analysis ensured that the optimal points are stable fot the controlled current source based on voltage detection regardeless the power elements variation. The APLCs control operates to damp THD and IHD constrains cooperating with each other without any communication. All studies, locatication, sizing and control, were tested in a real time plataform and proved to be feasiable.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9551
dc.date.accessioned2019-11-26T17:25:12Z
dc.date.available2019-11-26
dc.date.available2019-11-26T17:25:12Z
dc.typeTesept_BR
dc.subjectQualidade de Energia
dc.subjectDistorção Harmônica Total
dc.subjectMétodos de Otimização
dc.subjectControle Distribuído
dc.subjectCompensador Ativo de Potência
dc.subjectActive Power Line Conditioners (APLC)
dc.subjectDistorção Harmônica Individual (IHD)
dc.subjectPower Quality
dc.subjectTotal Harmonic Distortion
dc.subjectOptimization Methods
dc.subjectDistributed Control
dc.subjectIndividual Harmonic Distortion (IHD)
dc.rightsAcesso Abertopt_BR
dc.creatorGEHRKE, Camila Seibel.
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeLocation, sizing and control of active compensators in distribution networks.pt_BR
dc.identifier.citationGEHRKE, Camila Seibel. Localização, dimensionamento e controle de compensadores ativos em redes de distribuição. 2014. 182f. (Tese) Doutorado em Engenharia Elétrica, Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Campina Grande - Paraíba - Brasil, 2014.pt_BR
Appears in Collections:Doutorado em Engenharia Elétrica.

Files in This Item:
File Description SizeFormat 
CAMILA SEIBEL GEHRKE - TESE PPGEE 2014.pdfCamila Seibel Gehrke- Tese de Doutorado PPGEE 20144.42 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.