dc.creator.ID |
CAETANO, M. A. S. |
pt_BR |
dc.creator.Lattes |
http://lattes.cnpq.br/5656028750243919 |
pt_BR |
dc.contributor.advisor1 |
VIEIRA, Maria de Fátima Queiroz. |
|
dc.contributor.advisor1 |
SOUZA, Benemar Alencar de. |
|
dc.contributor.advisor1ID |
VIEIRA, M. F. Q. |
pt_BR |
dc.contributor.advisor1ID |
SOUZA, B. A. |
|
dc.contributor.advisor1Lattes |
http://lattes.cnpq.br/1459797138770378 |
pt_BR |
dc.contributor.advisor1Lattes |
http://lattes.cnpq.br/4987294390789975 |
|
dc.contributor.advisor2 |
SOUZA, Benemar Alencar de. |
|
dc.contributor.advisor2ID |
SOUZA, B. A. |
|
dc.contributor.advisor2Lattes |
http://lattes.cnpq.br/4987294390789975 |
|
dc.contributor.referee1 |
BRITO, Nubia Silva Dantas. |
|
dc.contributor.referee2 |
NEVES, Washington Luiz Araújo. |
|
dc.description.resumo |
O uso do formalismo de rede de Petri na modelagem dos sistemas de proteção e controle de
uma Usina Hidroelétrica e proposto. O objetivo foi implantar um sistema de diagnóstico de
falta em uma Usina visando apoiar o estudo de faltas e apoiar operadores quando da tomada
de decisão a qual passa a ser dar com base em um diagnostico mais preciso sobre a causa raiz
do desligamento da unidade geradora. O estudo se fundamentou na análise das proteções do
sistema, na análise do histórico de faltas do sistema contido nos relatórios de ocorrências
e no registro histórico do sistema super visório. Com o uso do aplicativo PIPE ("Plataform
Independent Petri Net Editor V4.2.1") foi possível modelar em redes de Petri as principais
proteções da usina e verificar a diminuição do numero de alarmes gerado numa ocorrência
com desligamento da unidade geradora, que chega a mais de 300 eventos para 5 eventos em
uma janela de analise da ocorrência que e de aproximadamente 5 minuto considerando o
tempo do disparo da proteção ate a parada total da unidade. A abordagem usando rede de
Petri proposto esta limitada em analisar as ocorrências causadas pela o disparo das proteções elétricas. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica |
|
dc.title |
Modelagem do sistema de proteção e controle de uma usina hidroelétrica para diagnóstico de falta. |
pt_BR |
dc.date.issued |
2014-10-31 |
|
dc.description.abstract |
The use of the formalism of Petri nets in modeling the protection and control systems of a
Hydroelectric Power. The objective is to implement a system of fault diagnosis in a power
plant to support the study of faults and provide an accurate and objective diagnosis of the
root cause of the shutdown of the generating unit, to support operators when making any
decision. The study was based on analysis of system protections, the historical analysis of
system faults contained in occurrence reports and historical record of the supervisor)' system.
Using the PIPE Application ("Platform Independent Petri Net Editor v4.2.1") was possible
to model Petri nets the main protections of the plant and verify the reduction of the number
of alarms generated in occurrence with shutdown of the generating unit, which reaches more
than 300 events to 5 events in an analysis window the event which is approximately five
minutes considering the protection tripping time to complete stoppage of the unit. The
proposed approach using Petri net is limited in analyzing the events caused by the firing
of electrical protections. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/10947 |
|
dc.date.accessioned |
2020-01-14T17:46:05Z |
|
dc.date.available |
2020-01-14 |
|
dc.date.available |
2020-01-14T17:46:05Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Usina Hidroelétrica |
|
dc.subject |
Redes de Petri |
|
dc.subject |
Sistema de Diagnóstico de Falta |
|
dc.subject |
Recomposição do Sistema de Geração |
|
dc.subject |
Inteligência Artificial |
|
dc.subject |
Hydroelectric Plant |
|
dc.subject |
Petri Nets |
|
dc.subject |
Fault Diagnosis System |
|
dc.subject |
Generation System Recomposition |
|
dc.subject |
Artificial Intelligence |
|
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
CAETANO, Marcos Antônio dos Santos. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Modeling of the protection and control system of a hydroelectric power plant for fault diagnosis. |
pt_BR |
dc.identifier.citation |
CAETANO, Marcos Antônio dos Santos. Modelagem do sistema de proteção e controle de uma usina hidroelétrica para diagnóstico de falta. 2014. 69 f. Dissertação (Mestrado em Engenharia Elétrica) – Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande, Paraíba, Brasil, 2014. |
pt_BR |