dc.description.resumo |
O desempenho de quatro isoladores de linhas de transmissão submetidos a 12 kV foram
avaliados considerando a poluição química no qual o isolador foi submetido. Um sistema de
processamento e aquisição de dados foi montado, a fim de permitir a classificação do nível
de contaminação, identificar a melhor faixa de frequência que contenha a assinatura espectral
dos isoladores e investigar qual polarização é mais apropriada para as medições, utilizando
uma abordagem estatística. Quando submetido a elevadas tensões, os isoladores irradiam sinais
de rádio frequência devido ao efeito corona. Métodos estatísticos como histogramas, teste de
normalidade e o coeficiente de correlação foram utilizados para classificar o nível de poluição em
isoladores de vidro. Mostra-se que, em determinadas situações os histogramas podem ser usados
para distinguir o estado de conservação dos isoladores. Ao utilizar o coeficiente de correlação
em conjunto com o teste de normalidade, é possível identificar faixas de frequência de interesse,
ou seja, faixas onde a assinatura espectral dos isoladores se encontra. Os testes foram limitados a
uma banda de 300 MHz (na de 30 MHz até 330 MHz), pois utilizar bandas maiores aumenta
demasiadamente o tempo necessário para aquisição de dados. Foram utilizados dois tipos de
antenas: bicônica e isotrópica (sensor 3D). Durante as medições com a antena bicônica, dois
tipos de polarização foram empregados, a polarização vertical e horizontal. A escolha de uma
antena (bicônica) com um dos tipos de polarização não considera sinais presentes nas demais
polarizações, ocasionando perda de informação relevante do sinal irradiado pelos isoladores.
Para investigar esse problema uma antena com características especiais foi empregada. Trata-se
do sensor 3D (antena isotrópica) que captura o sinal irradiado pelos isoladores nas polarizações
segundo os três eixos, fornecendo um único vetor campo elétrico que resume a polarização total
incidente. Medições realizadas com o sensor 3D foram confrontadas com as medições realizadas
com a antena linear, com o objetivo de verificar qual polarização leva a um melhor casamento
com a polarização do sinal irradiado pelos isoladores. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
pt_BR |
dc.title |
Utilização de um sensor de campo 3D e métodos estatísticos para diagnóstico de isoladores. |
pt_BR |
dc.date.issued |
2014-11 |
|
dc.description.abstract |
The insulating performance of four transmission lines subjected to 12 kV were evaluated
considering the chemical pollution of the insulator which has undergone. A system of data
acquisition and processing was mounted to enable the classification of the level of contamination,
to identify the best frequency band containing the spectral signature of the insulators and
investigate polarization which is more suitable for measurements using a statistical approach .
When subjected to high voltages, the insulator radiate radio frequency signals due to the corona
effect. Statistical methods such as histograms, test normality and the correlation coefficient were
used to rate the level of pollution in glass insulators. It is shown that in certain situations the
histograms can be used to distinguish the condition of the insulators. By using the correlation
coefficient in conjunction with the normality test can be identified frequency bands of interest,
or bands where the spectral signature is the insulators. Tests were limited to a band of 300
MHz (30 MHz to 330 MHz), for use higher bands excessively increases the time required for
data acquisition. Two types of antennas were used: biconical and isotropic (3D sensor). During
measurements with the biconical antenna, two types of polarization were used, the vertical and
horizontal polarization. The choice of antenna (biconical) with one type of polarization does not
consider the signals present in the other polarization, causing loss of relevant information of the
signal radiated by insulators. To investigate this problem an antenna with special features was
used. This is the 3D sensor (isotropic antenna) that captures the radiated signal by insulators
in polarizations based on the three, providing a single electric field vector that summarizes
the overall bias incident. Measurements with 3D sensor were compared with measurements
made with the linear antenna, in order to find what polarization leads to a better match with the
polarization of the radiated signal by insulators. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/18385 |
|
dc.date.accessioned |
2021-04-28T16:35:11Z |
|
dc.date.available |
2021-04-28 |
|
dc.date.available |
2021-04-28T16:35:11Z |
|
dc.type |
Trabalho de Conclusão de Curso |
pt_BR |
dc.subject |
Sensor de campo 3D |
pt_BR |
dc.subject |
Diagnóstico de isoladores |
pt_BR |
dc.subject |
Métodos estatísticos - diagnóstico de isoladores |
pt_BR |
dc.subject |
Estatística aplicada à Engenharia Elétrica |
pt_BR |
dc.subject |
Coeficiente de correlação |
pt_BR |
dc.subject |
Alta tensão |
pt_BR |
dc.subject |
Histogramas |
pt_BR |
dc.subject |
Sistema de aquisição de dados |
pt_BR |
dc.subject |
Isoladores de linhas de transmissão |
pt_BR |
dc.subject |
Isoladores de vidro - nível de poluição |
pt_BR |
dc.subject |
Antena bicônica |
pt_BR |
dc.subject |
Antena isotrópica |
pt_BR |
dc.subject |
Processamento de dados |
pt_BR |
dc.subject |
Variáveis qualitativa e quantitativa |
pt_BR |
dc.subject |
3D field sensor |
pt_BR |
dc.subject |
Insulator diagnostics |
pt_BR |
dc.subject |
Statistical methods - diagnosis of insulators |
pt_BR |
dc.subject |
Statistics applied to Electrical Engineering |
pt_BR |
dc.subject |
Correlation coefficient |
pt_BR |
dc.subject |
High voltage |
pt_BR |
dc.subject |
Histograms |
pt_BR |
dc.subject |
Data acquisition system |
pt_BR |
dc.subject |
Transmission line insulators |
pt_BR |
dc.subject |
Glass insulators - pollution level |
pt_BR |
dc.subject |
Biconical antenna |
pt_BR |
dc.subject |
Isotropic antenna |
pt_BR |
dc.subject |
Data processing |
pt_BR |
dc.subject |
Qualitative and quantitative variables |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
PEDRO, Haslan José Gonçalves. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Use of a 3D field sensor and statistical methods for diagnosing insulators. |
pt_BR |
dc.identifier.citation |
Haslan J. G. Pedro. Utilização de um sensor de campo 3D e métodos estatísticos para diagnóstico de isoladores. 2014. 88f. (Trabalho de Conclusão de Curso - Monografia), Curso de Bacharelado em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba - Brasil, 2014. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/18385 |
pt_BR |