Dimensionamento de MOV para proteção de bancos de capacitores série.

Mostrar el registro sencillo del ítem

dc.creator.ID BARBOSA, H. R. S. C. M. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/3242243452864584 pt_BR
dc.contributor.advisor1 DANTAS, Karcius Marcelus Colaço.
dc.contributor.advisor1ID DANTAS, K. M. C. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/1881990103809201 pt_BR
dc.contributor.referee1 LIRA, George Rossany Soares de.
dc.description.resumo Este trabalho mostra o procedimento para dimensionar os MOVs (Metal Oxide Varistors) dos Bancos de Capacitores Série (BCS) 05C5 e 05C6 localizados na Subestação de São João do Piauí. São determinadas as energias absorvidas por cada MOV para que estes sejam dimensionados corretamente para suportar as solicitações advindas de curto-circuito no sistema elétrico. O software ATP (Alternative Transient Program) foi utilizado para simular o sistema elétrico no horizonte de 2022 bem como o esquema elétrico dos BCS e o sistema de controle da proteção, este último utilizando a linguagem TACS. Foram determinados o nível de corrente de curto-circuito e energia a que os MOVs podem ser submetidos e que servem como parâmetro para realizar ou não o by-pass do BCS. Para isso simulou-se diversas faltas no sistema de forma a ajustar a proteção para as condições mais severas e avaliou-se o desempenho do ajuste encontrado. Também foi comparado o ajuste proposto com o atual e verificou-se que o ajuste vigente ficará obsoleto para o sistema do horizonte citado. Os parâmetros de ativação do Spark Gap por corrente foram superados, os de energia permaneceram próximos aos atuais. A energia nominal de um dos MOV, na linha Boa Esperança – São João do Piauí encontrada foi cerca de duas vezes o valor anterior, enquanto que a energia do MOV localizado no circuito 1 da linha entre São João do Piauí e Sobradinho permaneceu próxima ao valor anterior. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica. pt_BR
dc.title Dimensionamento de MOV para proteção de bancos de capacitores série. pt_BR
dc.date.issued 2018
dc.description.abstract This work shows the procedure for dimensioning the Metal Oxide Varistors (MOVs) of the Series Capacitor Banks (BCS) 05C5 and 05C6 located in the São João do Piauí Substation. The energies absorbed by each MOV are determined so that they are correctly sized to withstand short-circuit requests in the electrical system. The ATP (Alternative Transient Program) software was used to simulate the electrical system in the 2022 horizon as well as the electric scheme of the BCS and the protection control system, the latter using the TACS language. The level of short-circuit current and energy to which the MOVs can be submitted and which serve as a parameter to carry out BCS ¬by-pass or not is determined. For this, several faults were simulated in the system in order to adjust the protection for the most severe conditions and the performance of the found adjustment was evaluated. It was also compared the proposed adjustment with the current one and it was verified that the current adjustment will be obsolete for the system of the mentioned horizon. The parameters of activation of the Spark Gap by current were overcome, those of energy remained close to the current ones. The nominal energy of one of the MOVs in the Boa Esperança line - São João do Piauí found was about twice the previous value, while the MOV energy located in line 1 of the line between São João do Piauí and Sobradinho remained close to the value previous. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/18871
dc.date.accessioned 2021-05-18T20:55:13Z
dc.date.available 2021-05-18
dc.date.available 2021-05-18T20:55:13Z
dc.type Trabalho de Conclusão de Curso pt_BR
dc.subject Bancos de capacitores - proteção pt_BR
dc.subject MOV - dimensionamento pt_BR
dc.subject Proteção de bancos de capacitores pt_BR
dc.subject Dimensionamento de MOV pt_BR
dc.subject Compensação série pt_BR
dc.subject Capacitores série pt_BR
dc.subject Metal Oxide Varistor - MOV pt_BR
dc.subject Capacitor banks - protection pt_BR
dc.subject MOV - dimensioning pt_BR
dc.subject Protection of capacitor banks pt_BR
dc.subject Sizing of MOV pt_BR
dc.subject Series compensation pt_BR
dc.subject Series capacitors pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator BARBOSA, Hiago Richard Santa Cruz Martins.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Sizing of MOV for protection of series capacitor banks. pt_BR
dc.identifier.citation BARBOSA, Hiago Richard Santa Cruz Martins. Dimensionamento de MOV para proteção de bancos de capacitores série. 2018. 51f. (Trabalho de Conclusão de Curso - Monografia), Curso de Bacharelado em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba - Brasil, 2018. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/18871 pt_BR