dc.description.resumo |
A medição de resistência dinâmica (MRD) é uma técnica de diagnóstico
utilizada para aferir o grau de degradação dos contatos de disjuntores. A mesma se
destaca por ser capaz de analisar tanto os contatos principais como os de arco. Neste
trabalho é realizada uma análise da reprodutibilidade dos resultados de ensaios de MRD
implementados com e sem redução da velocidade de abertura dos contatos, além de uma
análise sobre a influência do nível de corrente de teste nos ensaios de MRD. Para avaliar
a metodologia, uma comparação foi feita utilizando o coeficiente de determinação (R2)
entre os resultados de MRD executadas com velocidade reduzida e com velocidade
nominal. Para realização dos ensaios, adotou-se um sistema alternativo de medição, que
consiste em um osciloscópio digital, uma bateria estacionária, sensores de tensão e
corrente e resistores de cromo-alumínio-ferro. O sistema proposto permite a aplicação
de uma corrente de teste de até 300 A. Para reduzir a velocidade de abertura dos
contatos, foi desenvolvido um sistema composto por um redutor de velocidade acoplado
a um motor assíncrono que, por sua vez, foi acionado por um inversor de frequência. A
partir dos resultados obtidos com as amostras estudadas, verificou-se que: os resultados
de MRD executadas com velocidade nominal de abertura dos contatos não se repetem
em ensaios similares; ensaios de MRD executados em velocidade nominal e utilizando
os níveis mínimos de corrente de teste indicados pelas normas IEC e ANSI são
altamente afetados pela interferência de películas de óleo, gerando diagnósticos
errôneos e/ou não confiáveis; ensaios de MRD realizados com velocidade reduzida de
abertura dos contatos fornecem maior reprodutibilidade dos resultados; para ensaios de
MRD realizados com velocidade reduzida, níveis maiores de corrente de teste ajudam a
aumentar a reprodutibilidade dos resultados, no entanto, este efeito diminui a medida
que a velocidade de abertura vai aumentando. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
pt_BR |
dc.title |
Ensaios de resistência dinâmica em disjuntores: análise de sensibilidade da corrente e da velocidade de abertura dos contatos. |
pt_BR |
dc.date.issued |
2015-06-23 |
|
dc.description.abstract |
The dynamic resistance measurement (DRM) is a diagnostic technique used to
assess the operative state of circuit breaker contacts, that stands out for being able to
analyze both the main and arcing contacts. In this research, an analysis of the result
reproducibility of DRM tests is presented, which was implemented with speed reduction
of the contact opening process, as well as an analysis of the test current level influence
on DRM results. To evaluate the methodology, a comparison was made using the
coefficient of determination (R2) between the results of the DRM tests carried out with
speed reduction and at rated speed. To perform the tests, an alternative system was
adopted, which consists of a digital oscilloscope, a stationary battery, current and
voltage sensors and resistors made of chrome aluminum iron. The proposed system
allows the injection of a direct current up to 300 A. To achieve the speed reduction of
the contact opening process, a speed reducer was coupled with an asynchronous motor,
which was triggered by a frequency inverter. From the obtained results with the samples
studied, it can be verified that: the results of DRM tests carried out with rated speed of
contact opening do not repeat themselves on similar tests; DRM tests carried out with
rated speed of contact opening and using the minimum levels of test current indicated
by IEC and ANSI standards are highly affected by the interference of oil films, thus,
providing masked and unreliable results; DRM tests carried out with reduced speed of
contact opening provides results with better reproducibility; for DRM tests carried out
with reduced speed of contact opening, higher levels of test current help to increase the
result reproducibility, however, this effect is not as noticeable as the opening speed
increases. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/19967 |
|
dc.date.accessioned |
2021-07-09T21:14:08Z |
|
dc.date.available |
2021-07-09 |
|
dc.date.available |
2021-07-09T21:14:08Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Disjuntores - ensaios de resistência |
pt_BR |
dc.subject |
Ensaios de resistência dinâmica - disjuntores |
pt_BR |
dc.subject |
Sensibilidade da corrente - análise |
pt_BR |
dc.subject |
Velocidade de abertura dos contatos |
pt_BR |
dc.subject |
Resistência dinâmica |
pt_BR |
dc.subject |
Corrente de teste |
pt_BR |
dc.subject |
Diagnóstico em disjuntores |
pt_BR |
dc.subject |
Disjuntores de alta tensão |
pt_BR |
dc.subject |
Manutenção em disjuntores |
pt_BR |
dc.subject |
Câmaras de extinção |
pt_BR |
dc.subject |
Câmaras de extinção |
pt_BR |
dc.subject |
Dynamic resistance tests - circuit breakers |
pt_BR |
dc.subject |
Current sensitivity - analysis |
pt_BR |
dc.subject |
Current sensitivity - analysis |
pt_BR |
dc.subject |
Dynamic resistance |
pt_BR |
dc.subject |
Test current |
pt_BR |
dc.subject |
Diagnosis in circuit breakers |
pt_BR |
dc.subject |
High voltage circuit breakers |
pt_BR |
dc.subject |
Maintenance on circuit breakers |
pt_BR |
dc.subject |
Extinction chambers |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
OLIVEIRA, Adriano Costa de. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Dynamic resistance tests on circuit breakers: analysis of current sensitivity and contact opening speed. |
pt_BR |
dc.identifier.citation |
OLIVEIRA, Adriano Costa de. Ensaios de resistência dinâmica em disjuntores: análise de sensibilidade da corrente e da velocidade de abertura dos contatos. 2015. 77f. (Dissertação de Mestrado) Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2015. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/19967 |
pt_BR |