dc.description.resumo |
Nesse trabalho foi realizado uma avaliação do comportamento transitório de
uma malha de aterramento submetida a correntes impulsivas, no domínio do tempo e
frequência, analisando a impedância transitória e impedância impulsiva (domínio do
tempo), e impedância harmônica (domínio da frequência) em relação a forma de onda e
amplitude da corrente injetada na malha de aterramento sob teste, no intuito de verificar
a qualidade da malha de aterramento sob solicitações de alta frequência, como também,
verificar os efeitos da ionização do solo e redução da resistividade do solo com o
aumento da frequência, na resposta transitória de uma malha de aterramento. Para isso,
foram utilizadas 4 configurações do gerador de impulso, resultando em 4 formas de
sinais de correntes impulsivas distintas, em que cada sinal foi injetada com 3 amplitudes
diferentes. Os resultados mostraram que quando a variável de análise foi a amplitude do
sinal de corrente impulsivo injetado, a impedância impulsiva e impedância transitória
não teve variação significativa. Também foi mostrado que quando a variável de análise
foi o tempo de frente do sinal de corrente impulsivo injetado, a impedância impulsiva
variou inversamente proporcional ao tempo de frente do sinal de corrente aplicado e a
impedância transitória estabiliza-se em torno da resistência em baixa frequência. O
módulo da impedância harmônica não teve alterações significativas quando comparada
a amplitude da corrente injetada, para as formas de onda de corrente com o mesmo
tempo de frente, atingindo seu máximo em torno de 1 MHz, para todos os casos
estudados. A fase da impedância harmônica não teve alterações significativas quando
comparada a amplitude da corrente injetada. Quando se analisou a fase da impedância
harmônica com relação às formas de onda observou-se que a malha de aterramento sob
teste tem comportamento predominantemente indutivo. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
pt_BR |
dc.title |
Análise de resposta de uma malha de aterramento submetida a correntes impulsivas por meio de resultados experimentais. |
pt_BR |
dc.date.issued |
2016-03-23 |
|
dc.description.abstract |
In this work, an experimental assessment of a ground grid behavior when
subjected to impulsive currents was performed, both in the time and in the frequency
domain, analyzing transient impedance and pulse impedance (time domain), and
harmonic impedance (frequency domain) relative to the front time, fall time and
amplitude of the current injected into the ground grid under test, in order to evaluate its
quality under high frequency applications, and also validate the obtained results by
using computer models in the time and frequency domain. For this purpose, four
different pulse generator settings were used, resulting in four distinct impulsive current
wave forms, wherein each wave form was injected into 3 different amplitudes.
The results showed that when the analysis variable was the injected current
amplitude, the impulsive impedance had no significant variation. It was also shown that
when the analysis variable was the front time of the applied current signal, the
impulsive impedance varied inversely proportional to the front time of the applied
current signal. When the harmonic impedance module related to the three impulsive
current amplitudes injected was analyzed, it was concluded that: the harmonic
impedance module had no significant changes compared to the injected current
amplitude, to the current waveforms with the same front time. When the harmonic
impedance module related to the four waveforms was analyzed, it was observed that: for
all studied cases, the harmonic impedance module is constant for frequencies below 100
kHz and, above this frequency, the module had its value increased, reaching its highest
value at around 1 MHz. The phase of the harmonic impedance had no significant
changes compared the amplitude of the injected current. When we analyzed the phase of
the harmonic impedance with respect to the waveforms observed that electric grounding
is predominantly inductive behavior. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20192 |
|
dc.date.accessioned |
2021-07-22T17:35:03Z |
|
dc.date.available |
2021-07-22 |
|
dc.date.available |
2021-07-22T17:35:03Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Malha de aterramento - análise de resposta |
pt_BR |
dc.subject |
Correntes impulsivas |
pt_BR |
dc.subject |
Impedância impulsiva |
pt_BR |
dc.subject |
Impedância transitória |
pt_BR |
dc.subject |
Impedância harmônica |
pt_BR |
dc.subject |
Aterramento elétrico |
pt_BR |
dc.subject |
Descargas atmosféricas |
pt_BR |
dc.subject |
Impulso de corrente - ensaios |
pt_BR |
dc.subject |
Ground loop - response analysis |
pt_BR |
dc.subject |
Impulsive currents |
pt_BR |
dc.subject |
Impulsive impedance |
pt_BR |
dc.subject |
Transient impedance |
pt_BR |
dc.subject |
Harmonic impedance |
pt_BR |
dc.subject |
Electrical ground |
pt_BR |
dc.subject |
Atmosferic discharges |
pt_BR |
dc.subject |
Current impulse - tests |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
ARAÚJO, Felipe José Lucena de. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Response analysis of a ground loop subjected to impulsive currents through experimental results. |
pt_BR |
dc.identifier.citation |
ARAÚJO, Felipe José Lucena de. Análise de resposta de uma malha de aterramento submetida a correntes impulsivas por meio de resultados experimentais. 2016. 76f. (Dissertação de Mestrado) Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2016. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20192 |
pt_BR |