DSpace/Manakin Repository

Avaliação da influência das forças eletromagnéticas nos entreferros de transformadores de corrente de proteção.

Mostrar registro simples

dc.creator.ID FERREIRA, R. S. A. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/1009418948225054 pt_BR
dc.contributor.advisor1 COSTA, Edson Guedes da.
dc.contributor.advisor1ID COSTA, E. G. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/3930289115658143 pt_BR
dc.contributor.advisor2 GUERRA, Francisco das Chagas Fernandes.
dc.contributor.advisor2ID GUERRA, F. C. F. pt_BR
dc.contributor.advisor2Lattes http://lattes.cnpq.br/1912783247913427 pt_BR
dc.contributor.referee1 NEVES, Washington Luiz Araújo.
dc.contributor.referee1ID NEVES, W. L. A. pt_BR
dc.contributor.referee2 LUCIANO, Benedito Antonio.
dc.contributor.referee2ID LUCIANO, B. A. pt_BR
dc.contributor.referee3 FERREIRA, Tarso Vilela.
dc.contributor.referee3ID FERREIRA, T. V. pt_BR
dc.description.resumo Neste trabalho é apresentada uma avaliação da influência das forças eletromagnéticas nos entreferros de transformadores de corrente de proteção. A avaliação é desenvolvida a partir da verificação da resposta transitória de transformadores de corrente de proteção, considerando os deslocamentos nos entreferros provocados pelas forças eletromagnéticas. Para tanto, foi avaliada a influência das forças eletromagnéticas no núcleo de transformadores de corrente com 8 mm, 16 mm e 24 mm, de comprimento efetivo do entreferro e em seguida, com diferentes distribuições de entreferros no núcleo. A partir do desenvolvimento de simulações computacionais baseadas no Método dos Elementos Finitos, foi possível determinar as forças eletromagnéticas e os deslocamentos nos entreferros. De acordo com os resultados obtidos nesta pesquisa, concluiu-se que as forças eletromagnéticas que atuam nos entreferros de transformadores de corrente de proteção, em condições de regime permanente e curto-circuito, não influenciam a resposta do transformador de corrente para nenhum dos casos avaliados. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica. pt_BR
dc.title Avaliação da influência das forças eletromagnéticas nos entreferros de transformadores de corrente de proteção. pt_BR
dc.date.issued 2017-12-04
dc.description.abstract The evaluation of the influence of electromagnetic forces in the gaps of protective current transformers is presented in this work. The evaluation is developed from the verification of the transient response of protective current transformers, considering the displacements in the gaps caused by the electromagnetic forces. Therefore, it was evaluated the influence of the electromagnetic forces for protective current transformers with 8 mm, 16 mm and 24 mm gap length, and then, with different gap distributions in the core. The development of computational simulations based on the Finite Element Method, made it possible to determine the electromagnetic forces and the displacements in the gaps. According to the results obtained in this research, it was concluded that the electromagnetic forces acting on the protective current transformer gaps, under conditions of permanent regime and short circuit, do not influence the current transformer response for any of the cases evaluated. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20226
dc.date.accessioned 2021-07-23T18:40:44Z
dc.date.available 2021-07-23
dc.date.available 2021-07-23T18:40:44Z
dc.type Dissertação pt_BR
dc.subject Forças eletromagnéticas pt_BR
dc.subject Transformadores de corrente de proteção pt_BR
dc.subject Eletromecânica pt_BR
dc.subject Curto-circuito pt_BR
dc.subject Entreferros - deslocamento pt_BR
dc.subject Método dos elementos finitos pt_BR
dc.subject Simulação multifísica pt_BR
dc.subject Corrente de curto-circuito pt_BR
dc.subject Histerese Jiles-Atherton - modelo pt_BR
dc.subject Electromagnetic forces pt_BR
dc.subject Protective Current Transformers pt_BR
dc.subject Electromechanical pt_BR
dc.subject Short circuit pt_BR
dc.subject Air gaps - displacement pt_BR
dc.subject Finite element method pt_BR
dc.subject Multiphysics simulation pt_BR
dc.subject Short circuit current pt_BR
dc.subject Jiles-Atherton Hysteresis - Model pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator FERREIRA, Regelii Suassuna de Andrade.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Evaluation of the influence of electromagnetic forces on the air gaps of protective current transformers. pt_BR
dc.identifier.citation FERREIRA, Regelli Suassuna de Andrade. Avaliação da influência das forças eletromagnéticas nos entreferros de transformadores de corrente de proteção. 2017. 72f. (Dissertação de Mestrado) Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2017. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20226 pt_BR


Arquivos deste item

Este item aparece na(s) seguinte(s) coleção(s)

Mostrar registro simples

Buscar DSpace


Busca avançada

Navegar

Minha conta