dc.description.resumo |
Os transformadores de potência com isolamento imerso em óleo mineral isolante são
equipamentos de tecnologia consolidada, pouca alteração tem sido acrescentada aos projetos
ao longo das últimas décadas. A mudança de cenário para um crescimento mais acentuado do
Sistema Elétrico de Potência brasileiro necessita de potências bem maiores e, para
acompanhar este crescimento em tempo hábil, o Operador Nacional do Sistema decidiu em
2011 exigir equipamentos que possam suportar sobrecargas diárias de longa e curta duração
de 20% e 40%, respectivamente. Este requisito tem conseqüências diretas no projeto dos
equipamentos, e também no projeto dos equipamentos das conexões aos transformadores nas
subestações, secionadores, disjuntores, transformadores de corrente e nos barramentos em
instalações antigas. A especificação técnica da Chesf foi alterada visando a atender às
condições de sobrecarga. No entanto, o estudo do comportamento térmico dos
transformadores de potência merece uma atenção especial desde a concepção dos
equipamentos. Este trabalho tem o intuito de avaliar o projeto térmico de transformadores de
potência adquiridos pela Chesf nos últimos dois anos através da análise de curvas da
temperatura de hot-spot. É desejado que os resultados venham a contribuir e respaldar os
requisitos técnicos das futuras especificações técnicas. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
pt_BR |
dc.title |
Análise de desempenho térmico de transformadores de potência com ciclo diário de sobrecarga planejada. |
pt_BR |
dc.date.issued |
2014-10-31 |
|
dc.description.abstract |
The oil-immersed transformers are consolidated technology equipment; little change has been
added to the projects over the last decades. A change of scenery for stronger growth of the
Brazilian Electric Power System needs more powers and to follow this growth during a
transitional period, the National System Operator decided in 2011 to require equipment able
to withstand diary load cycle with long and short overloading of 20% and 40%. This
requirement has direct consequences in the design of equipment, and also in the design of
other equipment from these transformers connections in substations, like switch disconnectors
, circuit breakers, current transformers and buses in older installations. Chesf transformers
technical specification was changed in order to meet these conditions of overload. However,
the study of the thermal behavior of power transformers deserves special attention since the
design of the equipment. This work aims to evaluate the thermal design of power transformers
from Chesf system acquired in the last two years, through the analysis of temperature curves
of hot-spot. It is desired that the results will contribute and support the technical requirements
of future technical specifications. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20233 |
|
dc.date.accessioned |
2021-07-23T19:27:35Z |
|
dc.date.available |
2021-07-23 |
|
dc.date.available |
2021-07-23T19:27:35Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Transformadores de potência - desempenho térmico |
pt_BR |
dc.subject |
Sobrecarga planejada |
pt_BR |
dc.subject |
Ciclo diário de sobrecarga planejada |
pt_BR |
dc.subject |
Curvas de hot-spot |
pt_BR |
dc.subject |
Hot-spot |
pt_BR |
dc.subject |
Transformadores com óleo isolante |
pt_BR |
dc.subject |
Sistema térmico de transformador |
pt_BR |
dc.subject |
Óleo mineral - transformadores |
pt_BR |
dc.subject |
Comutadores em carga |
pt_BR |
dc.subject |
Power transformers - thermal performance |
pt_BR |
dc.subject |
Planned overload |
pt_BR |
dc.subject |
Planned overload daily cycle |
pt_BR |
dc.subject |
Hot-spot curves |
pt_BR |
dc.subject |
Transformers with insulating oil |
pt_BR |
dc.subject |
Transformer Thermal System |
pt_BR |
dc.subject |
Mineral oil - transformers |
pt_BR |
dc.subject |
On-load switches |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
XAVIER, Cinthia Souza dos Santos. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Thermal performance analysis of power transformers with daily planned overload cycle. |
pt_BR |
dc.identifier.citation |
XAVIER, Cinthia Souza dos Santos. Análise de desempenho térmico de transformadores de potência com ciclo diário de sobrecarga planejada. 2014. 91f. (Dissertação de Mestrado) Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2014. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20233 |
pt_BR |