DSpace/Manakin Repository

Classificação de isoladores de vidro de alta tensão a partir do espectro eletromagnético irradiado.

Mostrar registro simples

dc.creator.ID ROCHA, P. H. V. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/4263182713137336
dc.contributor.advisor1 FONTGALLAND, Glauco.
dc.contributor.advisor1ID FONTGALLAND, G. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/4256595317953538 pt_BR
dc.description.resumo Os isoladores vítreos de alta tensão são, ainda hoje, os principais equipamentos empregados nas linhas de transmissão. Embora haja uma tendência de substituição desses por poliméricos, ainda são predominantemente encontrados principalmente nas redes de transmissão em alta tensão de 69 kV, 230 kV e 500 kV. Localizados distribuidamente ao longo de uma extensa área territorial, os métodos e procedimentos de inspeção se tornam de difícil execução. As rotinas de inspeções preventivas e preditivas realizadas atualmente são dotadas de bastante subjetividade e possuem muitos fatores que restringem a sua implementação. Dependem exclusivamente da avaliação visual do técnico e em condições climáticas específicas: período noturno, mínima fonte de luminosidade, principalmente da lua, umidade relativa do ar elevada e o uso de binóculo. Outras técnicas de inspeção foram estudadas, porém não foram encontrados relatos da sua utilização nas empresas de energia, para as tensões mencionadas. Este trabalho apresenta um método para a realização de inspeção em isoladores de alta tensão. O diferencial do método está na utilização de técnicas de processamento de sinais em conjunto com inteligência artificial, para que assim o espectro eletromagnético irradiado por esses equipamentos, quando estão em operação, seja interpretado e classificado quanto ao nível de poluição dos isoladores. Assim, um critério objetivo é inserido no processo, proporcionando ao inspetor uma ferramenta mais eficiente e que não necessite exclusivamente de uma avaliação subjetiva. As redes neurais artificiais realizaram a classificação dos sinais após o processamento desses através da transformada Wavelet. Medições em laboratório e em campo foram realizadas para servirem de base de dados para o treinamento do método. Os melhores resultados mostram acertos acima de 96,5% em todas as medições realizadas. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica. pt_BR
dc.title Classificação de isoladores de vidro de alta tensão a partir do espectro eletromagnético irradiado. pt_BR
dc.date.issued 2014-12
dc.description.abstract The glass high voltage insulators are, today, the main equipment used in transmission lines. Although a trend towards replacing them with polymers, are still predominantly found mainly in transmission networks for high voltage 69 kV, 230 kV and 500 kV. Located over an extensive geographical area, the methods and inspection procedures become difficult to perform. The routines of preventive and predictive inspections performed today are equipped with enough subjectivity and have many factors that restrict its implementation. Depend solely on the visual assessment of the technical and specific climatic conditions: night, minimum source of light, especially the moon, high relative humidity and the use of binoculars. Other inspection techniques were studied, but have not found reports of their use in energy companies, for the mentioned tensions. This research presents a method for carrying out inspection on high voltage insulators. The differential method is the use of set in signal processing techniques with artificial intelligence, so that the electromagnetic spectrum radiated by the equipment when in operation, should be interpreted and classified according to the level of pollution of the insulators. Thus, an objective criterion is inserted in the process, giving the inspector a more efficient tool that does not require only a subjective assessment. Artificial neural networks performed the classification of signals after processing these through the wavelet transform. Measurements in the laboratory and field tests were conducted to serve as a database for training method. The best results show up hit 96.5% in all measurements. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20248
dc.date.accessioned 2021-07-26T17:00:45Z
dc.date.available 2021-07-26
dc.date.available 2021-07-26T17:00:45Z
dc.type Dissertação pt_BR
dc.subject Isoladores de vidro de alta tensão pt_BR
dc.subject Espectro eletromagnético irradiado pt_BR
dc.subject Isoladores de alta tensão pt_BR
dc.subject Redes neurais artificiais pt_BR
dc.subject Reconhecimento de padrões pt_BR
dc.subject Transformada de Wavelet pt_BR
dc.subject High Voltage Glass Insulators pt_BR
dc.subject Radiated electromagnetic spectrum pt_BR
dc.subject High voltage insulators pt_BR
dc.subject Artificial neural networks pt_BR
dc.subject Pattern Recognition pt_BR
dc.subject Wavelet Transform pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator ROCHA, Pedro Henrique Venske da.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Classification of high voltage glass insulators from the radiated electromagnetic spectrum. pt_BR
dc.identifier.citation ROCHA, Pedro Henrique Venske da. Classificação de isoladores de vidro de alta tensão a partir do espectro eletromagnético irradiado. 2014. 101f. (Dissertação de Mestrado) Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2014. Disponível em: http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/20248 pt_BR


Arquivos deste item