Avaliação de sobre aquecimento anômalos em cabos elétricos de parque eólicos.

Mostrar registro simples

dc.creator.ID DIAS, R. A. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/5387063970690504 pt_BR
dc.contributor.advisor1 COSTA, Edson Guedes da.
dc.contributor.advisor1ID COSTA, E. G. pt_BR
dc.contributor.advisor1ID Costa, E. G. pt_BR
dc.contributor.advisor1ID E. C. Guedes. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/3930289115658143 pt_BR
dc.contributor.advisor2 LIRA, George Rossany Soares de.
dc.contributor.advisor2ID LIRA, G. R. S. pt_BR
dc.contributor.advisor2ID LIRA, GEORGE R. S pt_BR
dc.contributor.advisor2ID SOARES DE LIRA, GEORGE ROSSANY. pt_BR
dc.contributor.advisor2Lattes http://lattes.cnpq.br/7283717300126094 pt_BR
dc.contributor.referee1 NEVES, Washington Luiz Araújo.
dc.contributor.referee1ID NEVES, W. L. A. pt_BR
dc.contributor.referee1ID NEVES, WASHINGTON L.A. pt_BR
dc.contributor.referee1ID NEVES, W. L. A;NEVES, WASHINGTON LUIZ ARAUJO. pt_BR
dc.contributor.referee1Lattes http://lattes.cnpq.br/3107104665517286 pt_BR
dc.contributor.referee2 LUCIANO, Benedito Antonio.
dc.contributor.referee2ID LUCIANO, B. A. pt_BR
dc.contributor.referee2ID LUCIANO, BENEDITO ANTONIO. pt_BR
dc.contributor.referee2ID LUCIANO, B.A. pt_BR
dc.contributor.referee2Lattes http://lattes.cnpq.br/2390722791029216 pt_BR
dc.contributor.referee3 DANTAS, Karcius Marcelus Colaço.
dc.contributor.referee3ID DANTAS, K. M. C. pt_BR
dc.contributor.referee3ID Dantas, Karcius Marcelus Colaço. pt_BR
dc.contributor.referee3ID DANTAS, KARCIUS M. C. pt_BR
dc.contributor.referee3Lattes http://lattes.cnpq.br/1881990103809201 pt_BR
dc.description.resumo Neste trabalho foi avaliada a qualidade da energia elétrica e eficiência energética em parques eólicos, tendo como principal foco a análise do efeito pelicular provocado por harmônicos nos cabos da instalação de um parque eólico real. Utilizaram-se dados medidos em campo em estudo de qualidade da energia elétrica realizada para obtenção de acesso junto ao operador do sistema elétrico. Para a obtenção dos valores de distorções harmônicas das correntes medidas em campanha, utilizou-se o software HarmZs, comumente aplicado em estudos de qualidade. Os parques estudados apresentaram problemas na qualidade da energia entregue no ponto de conexão comum ao sistema elétrico interligado nacional. Nos cálculos das perdas adicionais ao sistema interno do parque, foi verificado um aumento de até 8% causado pelas correntes harmônicas na instalação do parque eólico. Com o auxílio do software COMSOL Multiphysics®, foi avaliada a distribuição da densidade de corrente resultante das correntes harmônicas nos cabos que conectam o aerogerador ao transformador elevador, cabos estes que apresentam maiores distorções de correntes harmônicas. Verificou-se que os cabos adjacentes interferem na distribuição de densidade de corrente e que o aumento da densidade de corrente na extremidade do cabo pode chegar a 68% quando comparado para o caso em que não há interferência de cabos adjacentes. Por fim, a analise térmica nos cabos indicou uma temperatura elevada, 136°C, para os condutores da fase B. O aumento de temperatura constatado pode ser atribuído, principalmente, às perdas decorrentes da corrente de componente fundamental e pelo processo de condução térmica entre fases. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica pt_BR
dc.title Avaliação de sobre aquecimento anômalos em cabos elétricos de parque eólicos. pt_BR
dc.date.issued 2018-08-13
dc.description.abstract This work evaluates power quality and energy efficiency in wind farms. The main focus is the analysis of the skin effect caused by harmonics in the cables of real wind farm installation. Data presented in the study of power quality performed to obtain access to the electric system operator, was used for the development of this research. The software HarmZs, commonly used in power quality studies, was used to obtain the harmonic distortion values for currents measured at wind farm site. The wind farm presented problems in the power quality delivered at the point of common connection to the national electrical power system. The additional losses calculations for the wind farm internal system presented an increase of up to 8% caused by the harmonic currents in the installation of the wind farm. With the aid of the software COMSOL Multiphysics®, the current density distributions from the harmonic currents in the cables were evaluated. The cables used for this study are implemented in the connection between wind turbine and elevator transformer. These cables present greater harmonic current distortions. It has been found that adjacent cables interfere with current density distribution and that the current density increase at cable end can reach 68% when compared to the case where there is no interference from adjacent cables. Finally, the thermal analysis in the cables indicated an elevated temperature, 136oC, for the conductors of phase B. The increase of temperature observed can be mainly attributed to the losses due to the fundamental component current and the process of thermal conduction between phases. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/26427
dc.date.accessioned 2022-07-25T17:46:38Z
dc.date.available 2022-07-22
dc.date.available 2022-07-25T17:46:38Z
dc.type Dissertação pt_BR
dc.subject Energia Elétrica – Qualidade pt_BR
dc.subject Eficiência Energética pt_BR
dc.subject Distorções Harmônicas pt_BR
dc.subject Parques Eólicos – Perdas por Harmônicos pt_BR
dc.subject Electric Power - Quality pt_BR
dc.subject Energy Efficiency pt_BR
dc.subject Harmonic Distortions pt_BR
dc.subject Wind Farms - Losses by Harmonics pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator DIAS, Ramon Araújo.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Evaluation of anomalous overheating in electrical cables of wind farm. pt_BR
dc.identifier.citation DIAS, Ramon Araújo. Avaliação de sobre aquecimento anômalos em cabos elétricos de parque eólicos. 2018. 85 fl. Dissertação (Mestrado em Engenharia Elétrica), Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2018. pt_BR