DSpace/Manakin Repository

Análise comparativa entre duas metodologias de estudo de coordenação de isolamentos para surtos atmosféricos em uma subestação de 500 kV da CHESF.

Mostrar registro simples

dc.creator.ID CRUZ, A. L. P. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/3909713879661809 pt_BR
dc.contributor.advisor1 NEVES, Washington Luiz Araújo.
dc.contributor.advisor1ID NEVES, W. L. A. pt_BR
dc.contributor.advisor1ID NEVES, WASHINGTON L.A. pt_BR
dc.contributor.advisor1ID NEVES, WASHINGTON LUIZ ARAUJO. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/3107104665517286 pt_BR
dc.contributor.referee1 FERNANDES JÚNIOR, Damásio.
dc.contributor.referee1ID FERNANDES Jr. D. pt_BR
dc.contributor.referee1ID FERNANDES, D. pt_BR
dc.contributor.referee1ID FERNANDES, DAMÁSIO. pt_BR
dc.contributor.referee1Lattes http://lattes.cnpq.br/3630883713661678 pt_BR
dc.contributor.referee2 COSTA, Edson Guedes da.
dc.contributor.referee2ID COSTA, E. G. pt_BR
dc.contributor.referee2ID COSTA, EDSON G. pt_BR
dc.contributor.referee2ID COSTA, E.G. DA. pt_BR
dc.contributor.referee2Lattes http://lattes.cnpq.br/3930289115658143 pt_BR
dc.description.resumo Neste trabalho apresenta-se uma análise comparativa entre duas metodologias de modelagem de componentes no programa Alternative Transients Program - ATP para estudos de transitórios eletromagnéticos de frente rápida, associados a descargas atmosféricas em linhas de transmissão incidindo numa subestação Extra Alta Tensão. Para este fim, um estudo de caso numa subestação de 500 kV da CHESF foi realizado considerando-se uma metodologia de modelagem simplificada (modelagem do surto por uma fonte de tensão) e atualmente utilizada no Brasil, bem como uma metodologia que considera a representação mais detalhada da linha de transmissão atingida pelo raio (modelagem do surto por uma fonte de corrente). para este último, foi definido um caso de referência em que foram selecionados alguns modelos propostos para a corrente de retorno, linha de transmissão, torres, suportabilidade da cadeia de isoladores e aterramento. Uma correlação entre o tempo de frente e a amplitude da corrente de descarga foi considerada no cado de referência. Para as duas metodologias analisadas, são apresentadas os principais resultados obtidos nas simulações e seus impactos na coordenação de isolamentos da subestação são comentadas. Por fim, são feitas análises de sensibilidade com relação a parâmetros e modelos de alguns componentes da linha de transmissão atingida pela descarga atmosférica, de forma a melhor avaliar o impacto de cada um nas sobretensões máximas verificadas no interior da subestação de 500 kV. As análises indicam que a modelagem do surto por uma fonte de tensão produz resultados conservadores em relação àqueles observados na modelagem do surto por uma fonte de corrente, podendo onerar o projeto de uma subestação no que tange à sua coordenação de isolamento. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica pt_BR
dc.title Análise comparativa entre duas metodologias de estudo de coordenação de isolamentos para surtos atmosféricos em uma subestação de 500 kV da CHESF. pt_BR
dc.date.issued 2018-03-02
dc.description.abstract This work presents a comparative analysis between two component modeling methodologies in the Alternative Transients Program - ATP for studies of fast-front electromagnetic transients, associated with lightning strikes in transmission lines affecting an Extra High Voltage substation. For this purpose, a case study in a CHESF 500 kV substation was carried out considering a simplified modeling methodology (surge modeling by a voltage source) and currently used in Brazil, as well as a methodology that considers the most detail of the transmission line struck by lightning (surge modeling by a current source). for the latter, a reference case was defined in which some proposed models were selected for the return current, transmission line, towers, supportability of the insulator chain and grounding. A correlation between the front time and the amplitude of the discharge current was considered in the reference case. For the two methodologies analyzed, the main results obtained in the simulations are presented and their impacts on the coordination of substation insulation are commented. Finally, sensitivity analyzes are carried out in relation to parameters and models of some components of the transmission line affected by lightning, in order to better assess the impact of each one on the maximum overvoltages verified inside the 500 kV substation. The analyzes indicate that the modeling of the surge by a voltage source produces conservative results in relation to those observed in the modeling of the surge by a current source, being able to burden the design of a substation with regard to its insulation coordination. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/27227
dc.date.accessioned 2022-09-15T14:36:04Z
dc.date.available 2022-09-15
dc.date.available 2022-09-15T14:36:04Z
dc.type Dissertação pt_BR
dc.subject ATP pt_BR
dc.subject Coordenação de isolamentos pt_BR
dc.subject Backflashover pt_BR
dc.subject Linha de transmissão pt_BR
dc.subject Descarga atmosférica pt_BR
dc.subject Isolation coordination pt_BR
dc.subject Line of streaming pt_BR
dc.subject Atmospheric discharge pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator CRUZ, André Luiz Pereira da.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Comparative analysis between two coordination study methodologies of insulation for atmospheric surges in a 500 kV substation of the CHESF. pt_BR
dc.identifier.citation CRUZ, André Luiz Pereira da. Análise comparativa entre duas metodologias de estudo de coordenação de isolamentos para surtos atmosféricos em uma subestação de 500 kV da CHESF. 2018. 181 fl. Dissertação (Mestrado em Engenharia Elétrica), Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande - Paraíba - Brasil, 2018. pt_BR