DSpace/Manakin Repository

Localização de faltas em linhas de transmissão baseada em ondas viajantes.

Mostrar registro simples

dc.creator.ID LOPES, F. V. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/3155646870666658 pt_BR
dc.contributor.advisor1 NEVES, Washington Luiz Araújo.
dc.contributor.advisor1ID NEVES, W. L. A. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/3107104665517286 pt_BR
dc.contributor.advisor2 FERNANDES JÚNIOR, Damásio.
dc.contributor.advisor2ID FERNANDES JÚNIOR, D. pt_BR
dc.contributor.advisor2Lattes http://lattes.cnpq.br/3630883713661678 pt_BR
dc.contributor.referee1 LEITÃO, José Júlio de Almeida Lins.
dc.contributor.referee2 SOUZA, Benemar Alencar de.
dc.description.resumo Neste trabalho é apresentado um método para localização de faltas em linhas de transmissão monitoradas em dois terminais. O algoritmo se baseia na detecção de transitórios por meio da aplicação da Transformada de Park aos sinais de tensão capturados nos pontos monitorados da linha. Tal transformada origina um sistema referencial girante que permite o cálculo de sinais com comportamentos distintos para os casos do sistema operando normalmente e em condições de regime transitório e, consequentemente, torna possível a detecção de distúrbios em sistema elétricos. A avaliação e validação do método proposto são realizadas por meio de simulações digitais fazendo uso do software ATP. Para tanto, linhas reais e fictícias são consideradas. Utiliza-se o MATLAB® para gerar rotinas que possibilitem a realização de simulações automáticas, tornando possível avaliar e validar o método proposto por meio de grandes quantidades de simulações. Desta forma, são analisados casos com diferentes tipos/características de falta bem como é avaliada a influência de diferentes esquemas de transposição sob o procedimento de localização dos distúrbios nas linhas de transmissão em estudo. Apresentam-se resultados das localizações de faltas nas referidas linhas de transmissão sendo estes classificados como satisfatórios ou não satisfatórios dependendo dos níveis de erro verificados. As simulações digitais realizadas comprovam que a localização de faltas por meio do algoritmo proposto pode ser utilizada para diminuir o tempo de procura do defeito, uma vez que restringe bastante o campo de busca do problema e, por fornecer a localização da falta quase que imediatamente após a ocorrência do distúrbio, evita a análise pós-falta de registros oscilográficos normalmente realizada por métodos convencionais. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica.
dc.title Localização de faltas em linhas de transmissão baseada em ondas viajantes. pt_BR
dc.date.issued 2011-03-01
dc.description.abstract In this work is presented a method for fault location on transmission lines monitored in two terminals. The algorithm is based on the detection of transients through Park Transformation application on three-phase voltage signals in both ends of the line. Such transformation generates a rotating reference system that permits the calculation of signals with different behavior for the cases of the system operating normally and in transient conditions and, consequently, it is possible to detect disturbances in electrical power systems. The evaluation and validation of the proposed method are performed by means of digital simulations using the ATP software. For this purpose, real and fictitious transmission lines are considered. The MATLAB® is used to perform the simulations automatically. So, a lot of cases with different fault conditions in transmission lines with different transposition scheme are studied. Fault location results are presented and classified as satisfactory or not satisfactory depending on the value of the calculated error. Computer simulations prove that the fault location using the proposed method may decrease the search time of the fault because restricts de search field of the problem and, due to perform the fault location almost immediately after the disturbance occurrence, avoids the post-fault analysis of oscillographic records normally carried out by conventional methods. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/3219
dc.date.accessioned 2019-03-25T15:58:18Z
dc.date.available 2019-03-25
dc.date.available 2019-03-25T15:58:18Z
dc.type Dissertação pt_BR
dc.subject Faltas em Linhas de Transmissão.
dc.subject Linhas de Transmissão.
dc.subject Localização de Faltas.
dc.subject Transformada de Park.
dc.subject Transitórios Eletromagnéticos.
dc.subject Faults in Transmission Lines.
dc.subject Transmission lines.
dc.subject Fault location.
dc.subject Transform of Park.
dc.subject Electromagnetic Transients.
dc.rights Acesso Aberto pt_BR
dc.creator LOPES, Felipe Vigolvino.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Fault location on transmission lines based on traveling waves. pt_BR
dc.identifier.citation LOPES, Felipe Vigolvino. Localização de faltas em linhas de transmissão baseada em ondas viajantes. 2011. 94f. (Dissertação de Mestrado em Engenharia Elétrica), Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba Brasil, 2011. pt_BR