DSpace/Manakin Repository

Chave controlada para redução de sobretensões de manobra em linhas de transmissão.

Mostrar registro simples

dc.creator.ID CARDOSO, G. A. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/1847779552377372 pt_BR
dc.contributor.advisor1 NEVES, Washington Luiz Araújo.
dc.contributor.advisor1ID NEVES, W. L. A. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/3107104665517286 pt_BR
dc.contributor.advisor2 FERNANDES JÚNIOR, Damásio.
dc.contributor.advisor2ID FERNANDES JÚNIOR, D. pt_BR
dc.contributor.advisor2Lattes http://lattes.cnpq.br/3630883713661678 pt_BR
dc.contributor.referee1 SOUZA, Benemar Alencar de.
dc.contributor.referee2 MOTA, Wellington Santos.
dc.description.resumo Este trabalho apresenta um dispositivo de controle implementado em um DSP (Digital Signal Processor) para estimar o instante de fechamento dos contatos de um disjuntor em energizações e religamentos tripolares de linhas de transmissão, considerando carga residual e efeitos da compensação. O método do chaveamento controlado implementado no DSP é baseado em um algoritmo de detecção de passagens por zero. Para minimizar os efeitos da indução de tensão nas fases da linha de transmissão, o intervalo de tempo entre o fechamento do primeiro e do ultimo pólo é o menor possível. A chave controlada é testada em simulações em tempo real, utilizando o RTDS (Real-Time Digital Simulator) para modelar o sistema elétrico, que consiste em uma linha de transmissão fictícia (classe de tensão 550 kV e extensão 400 km), com parâmetros reais de parte do sistema da Companhia Hidro Elétrica do São Francisco (CHESF), duas fontes de tensão com impedância equivalente (uma em cada extremidade) e disjuntores. Na simulação, a chave controlada (DSP) recebe um sinal de comando do RTDS™ para fechamento do disjuntor. O sinal é atrasado de um intervalo de tempo tal que, o fechamento aconteça o mais próximo de uma passagem pelo zero da tensão entre os contatos do disjuntor. O sinal atrasado é então enviado de volta para o RTDS™ e o disjuntor é finalmente fechado no instante ótimo. A dispersão estatística no tempo de operação do disjuntor é considerada. Os resultados apresentados comprovam a eficiência do método do chaveamento controlado para reduzir sobretensões de manobra em linhas de transmissão. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica.
dc.title Chave controlada para redução de sobretensões de manobra em linhas de transmissão. pt_BR
dc.date.issued 2009-06
dc.description.abstract This work presents a control device implemented in a DSP (Digital Signal Processor) to estimate suitable times for closing and reclosing circuit breaker contacts during three-pole transmission line switching, taking into account trapped charges and line compensation effects. The controlled switching method implemented in the DSP is based on a simple zero crossing algorithm. In order to minimize the effect of the electromagnetic coupling between transmission line phases, the time span between the closing instant of the first and the last pole is as small as possible. The controlled switch is tested in a Real Time Digital Simulator (RTDS™) where was modeled the power system, that consists in a source, a fictitious transmission line (voltage class 550 kV and 400 km long) with real parameters of part of the network of Companhia Hidro Elétrica do São Francisco (CHESF), two equivalent sources and circuit breakers. In the simulation, the controlled switch (DSP) receives a command signal from the RTDS™ to close the circuit breaker, delays this command signal in a time interval such that the making instant of the breaker contacts is near the zero crossing voltage, and sends back the delay trip to the RTDS™ and the breaker is closed in a making instant. The statistical dispersion in the circuit breaker operation time is considered. The presented results are fairly good attesting the efficiency of the method to reduce switching overvoltages. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/3236
dc.date.accessioned 2019-03-26T10:28:28Z
dc.date.available 2019-03-26
dc.date.available 2019-03-26T10:28:28Z
dc.type Dissertação pt_BR
dc.subject Chaveamento Controlado.
dc.subject DSP.
dc.subject Linhas de Transmissão.
dc.subject RTDS™.
dc.subject Transitórios Eletromagnéticos.
dc.subject Sobretensões de Manobra.
dc.subject Controlled Switching.
dc.subject Transmission lines.
dc.subject Electromagnetic Transients.
dc.subject Maneuver overvoltages.
dc.rights Acesso Aberto pt_BR
dc.creator CARDOSO, Gustavo de Alcântara.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Controlled switch for reduction of switching overvoltages in transmission lines. pt_BR
dc.identifier.citation CARDOSO, Gustavo de Alcântara. Chave controlada para redução de sobretensões de manobra em linhas de transmissão. 2009. 69f. Dissertação (Mestrado em Engenharia Elétrica), Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba Brasil, 2009. pt_BR


Arquivos deste item

Este item aparece na(s) seguinte(s) coleção(s)

Mostrar registro simples

Buscar DSpace


Busca avançada

Navegar

Minha conta