dc.description.resumo |
As aplicações dos sistemas de aterramento em sistemas elétricos de potência exigem
baixos valores de resistência de aterramento em baixa frequência, da ordem de alguns
Ohms. Se o solo apresenta resistividade elevada, os eletrodos convencionais não
permitem alcançar o valor especificado de resistência, ou o fazem a um custo muito
elevado. Na tentativa de minimizar os efeitos das altas resistividades do solo, reduzindo
os valores das resistências de aterramento através de alternativas simples e práticas, este
trabalho busca um novo sistema de aterramento, com comportamento resistivo
semelhante ou inferior, quando comparado com os sistemas de aterramento
convencionais formados por hastes de cobre nu, e que seja minimamente afetado pelas
variações de umidade do solo. Duas novas concepções de sistemas de aterramento, com
o uso de hastes envolvidas em concreto e hastes envolvidas em concreto com bentonita
como aditivo, foram desenvolvidas. Os novos sistemas de hastes de aterramento terão
seu desempenho avaliado com medições periódicas da resistência de aterramento e
também com a aplicação impulsos de corrente de várias intensidades. Os resultados das
medições de resistência de aterramento mostraram que as hastes concretadas dependem
da acomodação do solo circunvizinho para a estabilização dos valores de resistência de
aterramento em baixa frequência. Os ensaios de impulso de corrente mostraram que a
hastes concretadas, com e sem bentonita, apresentam comportamento semelhante à
haste convencional (nua). A tensão de passo, sempre apresentou valores bem abaixo dos
limites máximos permitidos, no entanto as tensões de toque foram superiores aos limites
máximos permitidos, no tempo. Houve uma redução substancial nos valores da
impedância impulsiva de aterramento para hastes concretadas com e sem bentonita, com
o aumento da tensão de carregamento, consequentemente, com o aumento da tensão
estabelecida nos terminais das hastes. Todas as hastes concretadas suportaram aos
esforços produzidos pelas altas correntes sem apresentar rupturas na estrutura de
concreto. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
|
dc.title |
Avaliação do desempenho de novas concepções de malhas de aterramento. |
pt_BR |
dc.date.issued |
2012-03 |
|
dc.description.abstract |
The grounding of an electrical system is essentially an electrical connection to the
ground, where the value of grounding resistance represents the effectiveness of this
connection: the lower the resistance, the better the grounding. Some applications require
low values of grounding resistance, about a few ohms, even if a the area available for
electrodes placement is small. If the soil has high resistivity, conventional electrodes
cannot achieve the specified resistance value, and even if it does, the cost would be very
high. In an attempt to minimize the effects of the high resistivity of the soil, reducing
the values of grounding resistance through a simple and practical alternative, will be
sought a new grounding system that, with lower earthing resistance, independent of
changes in moisture levels soil compared to the conventional grounding system formed
by bare copper rods. Two new designs of grounding systems were developed using rods
involved in concrete and rods involved in concrete with bentonite as an additive. The
new systems of ground rods will have its performance assessed by applying current
impulses of various intensities and with periodic measurements of grounding resistance
at low frequency. Concreted rods depend on accommodation of surrounding soil to
stabilize the values of grounding resistance at low frequencies. The impulse tests
showed that the concreted rods, with and without bentonite, behavior is similar to that
of the conventional copper rod. The touch voltages were higher than the maximum
allowable limits. In the other hand and the step voltage, always showed values below
the maximum allowed. There was a substantial reduction in the impulsive impedance
values for concreted rods with and without bentonite, by increasing the charging voltage
thereby to increasing the voltage established at the terminals of the rods. All the
concreted rods supported the efforts produced by the high currents without presenting
breaks in the concrete structure. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/3289 |
|
dc.date.accessioned |
2019-03-28T16:06:44Z |
|
dc.date.available |
2019-03-28 |
|
dc.date.available |
2019-03-28T16:06:44Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Resistência - Engenharia Elétrica. |
|
dc.subject |
Sistemas de Aterramento. |
|
dc.subject |
Impulso de Corrente. |
|
dc.subject |
Resistance - Electrical Engineering. |
|
dc.subject |
Grounding Systems. |
|
dc.subject |
Current impulse. |
|
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
RODRIGUES, Maria Alice de Oliveira. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Evaluation of the performance of new conceptions of grounding meshes. |
pt_BR |
dc.identifier.citation |
RODRIGUES, Maria Alice de Oliveira. Avaliação do desempenho de novas concepções de malhas de aterramento. 2012. 83f. (Dissertação de Mestrado em Engenharia Elétrica), Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática , Universidade Federal de Campina Grande – Paraíba Brasil, 2012. |
pt_BR |