dc.description.resumo A energia solar fotovoltaica está em ascensão devido à redução nos custos de instalação, abundância do recurso solar, ao apelo ambiental e à simplicidade de instalação. No Brasil, a capacidade instalada em 2021 atingiu a marca de 10.429 MW, representando 2,1% de toda a matriz elétrica nacional. Contudo, a fonte solar apresenta elementos com características não lineares, tais como os inversores de corrente que, na conversão em corrente contínua (CC) para corrente alternada (CA) podem inserir distúrbios na Qualidade da Energia Elétrica (QEE), dentre os quais se destacam as distorções harmônicas de tensão. Por esta razão, no Brasil, o Operador Nacional do Sistema Elétrico (ONS) exige a execução de estudos teóricos e medições em campo de QEE, conforme diretrizes, critérios e premissas estabelecidos nos Procedimentos de Rede do Sistema Interligado Nacional (SIN), documentados em Submódulos (ONS, 2021), e nas instruções específicas publicadas pelo ONS. Desta forma, alinhado com tais diretrizes, critérios e premissas, o presente trabalho visa realizar um estudo comparativo de duas metodologias para determinação da distorção harmônica em um complexo solar real, conectado à Rede Básica em 230 kV, com potência nominal instalada de 135 MWac. Para tanto, as metodologias comparadas são: agregação simples (soma algébrica das correntes harmônicas) e agregação vetorial (aplicando o fator de agregação). Nas simulações, fez­ se uso do programa HarmZs – Estudos de Comportamento Harmônico e Análise Modal de Redes Elétricas, desenvolvido e mantido pelo CEPEL, para modelagem do complexo solar e obtenção dos resultados. A partir dos resultados obtidos, verificou­se que: para a agregação simples tem­se uma maior quantidade de componentes harmônicas que superaram os limites individuais estabelecidos pelo ONS, bem como o limite da distorção harmônica total. Por outro lado, usando a agregação vetorial, os resultados foram distintos e indicaram uma menor quantidade de componentes harmônicas que superaram os limites individuais, e a distorção harmônica total se mostrou inferior. Concluiu­se, portanto que, a depender da metodologia utilizada, pode haver um dimensionamento desnecessário de filtros de harmônicos. Diante dos distintos resultados, faz­se necessário realizar medições em campo, visando validar as metodologias e resultados aqui apresentados. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica pt_BR
dc.title Fator de agregação em estudos de qualidade da energia elétrica para usinas fotovoltaicas com inversores STRIN. pt_BR
dc.date.issued 2021-10-30
dc.description.abstract Due to reduced installation costs, abundance of solar resource, environmental appeal and simplicity of installation, the photovoltaic solar energy use is rising. In Brazil, the installed capacity in 2021 reached 10,429 MW, representing 2.1% of the entire national power matrix. However, the solar source has elements with non­linear characteristics, such as current inverters that, when converting from direct current (DC) to alternating current (AC), can cause disturbances in the Quality of Electric Power (QEE), among which, harmonic voltage distortions are highlighted. Therefore, in Brazil, the National Electric System Operator requires the execution of theoretical studies and field measurements of QEE, according to guidelines, criteria and assumptions established in the Network Procedures documented in Sub­modules (ONS, 2021) of the National Interconnected System (SIN), and in the specific instructions published by the ONS. In such a way, lining up with these guidelines, criteria and assumptions, this work aims to carry out a comparative study of two methodologies to point out the harmonic distortion in a real solar complex, connected to the Basic Network at 230 kV, with 135 MWac of nominal installed power. Therefore, the compared methodologies are: simple aggregation (algebraic sum of harmonic currents) and vector aggregation (applying the aggregation factor). In the simulations, the program HarmZs is used – Harmonic Behavior Studies and Modal Analysis of Electric Networks, developed and maintained by CEPEL, for modeling the solar complex and to obtain the results. It is verified from the results obtained, that: for a simple aggregation, there is a greater amount of harmonic components that surpassed the individual limits established by the ONS, as well as the total harmonic distortion limit. On the other hand, using vector aggregation, the results are different and indicate smaller amounts of harmonic components that surpassed the individual limits, and the total harmonic distortion is lower. Hence, it is concluded that, there may be an unnecessary dimensioning of harmonic filters depending on the methodology used. Due to different results, it is necessary make measurements in field, in order to validate the methodologies and results presented here. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/33077
dc.date.accessioned 2023-11-22T16:47:57Z
dc.date.available 2023-11-22
dc.date.available 2023-11-22T16:47:57Z
dc.type Trabalho de Conclusão de Curso pt_BR
dc.subject Qualidade da Energia Elétrica pt_BR
dc.subject Usinas Fotovoltaicas pt_BR
dc.subject Energia Solar Fotovoltaica pt_BR
dc.subject Geração Centralizada pt_BR
dc.subject Geração Solar pt_BR
dc.subject Inversores STRIN pt_BR
dc.subject Distorção Harmônica de Tensão pt_BR
dc.subject Electrical Power Quality pt_BR
dc.subject Photovoltaic Plants pt_BR
dc.subject Photovoltaic Solar Energy pt_BR
dc.subject Centralized Generation pt_BR
dc.subject Solar Generation pt_BR
dc.subject STRING Inverters pt_BR
dc.subject Voltage Harmonic Distortion pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator ALVES, Matheus Rocha.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Aggregation factor in electrical energy quality studies for photovoltaic plants with STRIN inverters. pt_BR
dc.identifier.citation ALVES, Matheus Rocha. Fator de agregação em estudos de qualidade da energia elétrica para usinas fotovoltaicas com inversores STRIN. 2021. 73 f. Monografia (Bacharelado em Engenharia Elétrica) - Universidade Federal de Campina Grande, Centro de Engenharia Elétrica e Informática, Campina Grande, 2021.