dc.description.resumo |
Os pára-raios à base de óxido de zinco são utilizados na proteção dos sistemas
elétricos. Eles atuam, como supressores de surtos, limitando a tensão e transformando parte da energia elétrica em energia térmica. Estudou-se os desempenhos elétricos e térmicos de páraraios de ZnO. O desempenho elétrico foi estudado através do desenvolvimento e uso de métodos práticos sob condições normais e anormais de serviços e, de ensaios em laboratórios. O desempenho térmico foi estudado através da propagação de calor em um pára-raios completo, em uma secção de teste, em um pára-raios hipotético e em uma secção de teste hipotética. Desse modo, um modelo eletrotérmico versátil foi desenvolvido. Estudos foram feitos analisando-se experimentos com simulações; simulações de pára-raios e secções de teste em ensaios exigidos por normas e simulações de configurações. As temperaturas obtidas nos ensaios experimentais executados com àquelas obtidas na simulação dos ensaios foram
comparadas para o pára-raios completo e secção de teste. A análise dos resultados obtidos das simulações x experimentos foi feita e mostra uma concordância muito boa, validando o modelo eletrotérmico computacional apresentado. O modelo eletrotérmico validado foi eficiente nas simulações dos ensaios exigidos pelas normas técnica e nas simulações das configurações propostas. Constatou-se, também, que a simulação numérica através de diferenças finitas utilizando formulação implícita, foi capaz de representar satisfatoriamente o perfil térmico de secções de teste e de pára-raios completos, quando submetidos a condições normais e anormais de serviços e, de ensaios em laboratório. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
pt_BR |
dc.title |
Análise do desempenho de para-raios de óxido de zinco. |
pt_BR |
dc.date.issued |
1999-03 |
|
dc.description.abstract |
Zinc oxide(ZnO)-based surge arresters are applied in electric power systems as protection
against overvoltages. The surge arresters limited the voltage peaks by transforming a part of the
electrical energy into thermal energy. The electro-thermal performance of ZnO surge arresters
has been studied during normal and abnormal service conditions and during laboratory tests.
For this purpose, an electro-thermal model has been proposed which initially computes the
energy input to the ZnO arrester for a given applied voltage. Subsequently, the computational
model determines the temperature distribution and its temporal variation by means of the
implicit formation of the method of finite differences.
The electro-thermal computational model has been used to study the performance of a
complete surge arrester and of a prorated section when subjected to laboratory tests. The
computed temperature distributions and their time variations have been compared with
experimental measurements. The good agreement between computed and measured results
validates the electro-thermal model.
The computational model has then used to study the performance of a hypothetical surge
arrester configuration and a prorated section of this configuration. The model is able to predict
the behaviour of the surge arrester during standard laboratory tests. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/3316 |
|
dc.date.accessioned |
2019-04-02T15:26:40Z |
|
dc.date.available |
2019-04-01 |
|
dc.date.available |
2019-04-02T15:26:40Z |
|
dc.type |
Tese |
pt_BR |
dc.subject |
Para-Raios de Óxido de Zinco |
pt_BR |
dc.subject |
Sobretensões |
pt_BR |
dc.subject |
Modelo Eletrotérmico |
pt_BR |
dc.subject |
ZnO - Para-Raios |
pt_BR |
dc.subject |
Estabilidade Térmica - Para-raios à ZnO |
pt_BR |
dc.subject |
Cálculo de Energia Absorvida |
pt_BR |
dc.subject |
Modelos Térmicos |
pt_BR |
dc.subject |
Modelos Matemáticos/Computacionais |
pt_BR |
dc.subject |
Descarga de Linha de Transmissão |
pt_BR |
dc.subject |
Descarga de Impulso de Corrente Atmosférica |
pt_BR |
dc.subject |
Transferência de Calor |
pt_BR |
dc.subject |
Modelo Térmico Computacional |
pt_BR |
dc.subject |
ZnO Arrester |
pt_BR |
dc.subject |
Zinc Oxide Lightning Arrester |
pt_BR |
dc.subject |
Thermal Stability - ZnO Surge Arresters |
pt_BR |
dc.subject |
Calculation of Absorbed Energy |
pt_BR |
dc.subject |
Download of Transmission Line |
pt_BR |
dc.subject |
Atmospheric Current Impulse Discharge |
pt_BR |
dc.subject |
Computational Thermal Model |
pt_BR |
dc.subject |
Heat Transfer |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
COSTA, Edson Guedes da. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Analysis of the performance of zinc oxide arresters. |
pt_BR |
dc.identifier.citation |
COSTA, Edson Guedes da. Análise do desempenho de para-raios de óxido de zinco. 1999. 201f. (Tese de Doutorado em Engenharia Elétrica). Programa de Pós-Graduação em Engenharia Elétrica, Centro de Ciências e Tecnologia, Universidade Federal da Paraíba - Campus II - Campina Grande, 1999. |
pt_BR |