Análise do desempenho de para-raios de óxido de zinco.

Mostrar registro simples

dc.creator.ID COSTA, E. G. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/3930289115658143 pt_BR
dc.contributor.advisor1 NAIDU, Sreeramulu Raghuram.
dc.contributor.advisor1ID NAIDU, S. R. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/1635797379532528 pt_BR
dc.contributor.referee1 GURGEL, José Maurício Alves de Matos.
dc.contributor.referee2 PISSOLATO FILHO, José.
dc.contributor.referee3 ARAÚJO, Antônio Emílio Angueth de.
dc.contributor.referee4 NEVES, Washington Luiz de Araújo.
dc.contributor.referee5 LIMA, Antônio Marcus Nogueira de.
dc.description.resumo Os pára-raios à base de óxido de zinco são utilizados na proteção dos sistemas elétricos. Eles atuam, como supressores de surtos, limitando a tensão e transformando parte da energia elétrica em energia térmica. Estudou-se os desempenhos elétricos e térmicos de páraraios de ZnO. O desempenho elétrico foi estudado através do desenvolvimento e uso de métodos práticos sob condições normais e anormais de serviços e, de ensaios em laboratórios. O desempenho térmico foi estudado através da propagação de calor em um pára-raios completo, em uma secção de teste, em um pára-raios hipotético e em uma secção de teste hipotética. Desse modo, um modelo eletrotérmico versátil foi desenvolvido. Estudos foram feitos analisando-se experimentos com simulações; simulações de pára-raios e secções de teste em ensaios exigidos por normas e simulações de configurações. As temperaturas obtidas nos ensaios experimentais executados com àquelas obtidas na simulação dos ensaios foram comparadas para o pára-raios completo e secção de teste. A análise dos resultados obtidos das simulações x experimentos foi feita e mostra uma concordância muito boa, validando o modelo eletrotérmico computacional apresentado. O modelo eletrotérmico validado foi eficiente nas simulações dos ensaios exigidos pelas normas técnica e nas simulações das configurações propostas. Constatou-se, também, que a simulação numérica através de diferenças finitas utilizando formulação implícita, foi capaz de representar satisfatoriamente o perfil térmico de secções de teste e de pára-raios completos, quando submetidos a condições normais e anormais de serviços e, de ensaios em laboratório. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica. pt_BR
dc.title Análise do desempenho de para-raios de óxido de zinco. pt_BR
dc.date.issued 1999-03
dc.description.abstract Zinc oxide(ZnO)-based surge arresters are applied in electric power systems as protection against overvoltages. The surge arresters limited the voltage peaks by transforming a part of the electrical energy into thermal energy. The electro-thermal performance of ZnO surge arresters has been studied during normal and abnormal service conditions and during laboratory tests. For this purpose, an electro-thermal model has been proposed which initially computes the energy input to the ZnO arrester for a given applied voltage. Subsequently, the computational model determines the temperature distribution and its temporal variation by means of the implicit formation of the method of finite differences. The electro-thermal computational model has been used to study the performance of a complete surge arrester and of a prorated section when subjected to laboratory tests. The computed temperature distributions and their time variations have been compared with experimental measurements. The good agreement between computed and measured results validates the electro-thermal model. The computational model has then used to study the performance of a hypothetical surge arrester configuration and a prorated section of this configuration. The model is able to predict the behaviour of the surge arrester during standard laboratory tests. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/3316
dc.date.accessioned 2019-04-02T15:26:40Z
dc.date.available 2019-04-01
dc.date.available 2019-04-02T15:26:40Z
dc.type Tese pt_BR
dc.subject Para-Raios de Óxido de Zinco pt_BR
dc.subject Sobretensões pt_BR
dc.subject Modelo Eletrotérmico pt_BR
dc.subject ZnO - Para-Raios pt_BR
dc.subject Estabilidade Térmica - Para-raios à ZnO pt_BR
dc.subject Cálculo de Energia Absorvida pt_BR
dc.subject Modelos Térmicos pt_BR
dc.subject Modelos Matemáticos/Computacionais pt_BR
dc.subject Descarga de Linha de Transmissão pt_BR
dc.subject Descarga de Impulso de Corrente Atmosférica pt_BR
dc.subject Transferência de Calor pt_BR
dc.subject Modelo Térmico Computacional pt_BR
dc.subject ZnO Arrester pt_BR
dc.subject Zinc Oxide Lightning Arrester pt_BR
dc.subject Thermal Stability - ZnO Surge Arresters pt_BR
dc.subject Calculation of Absorbed Energy pt_BR
dc.subject Download of Transmission Line pt_BR
dc.subject Atmospheric Current Impulse Discharge pt_BR
dc.subject Computational Thermal Model pt_BR
dc.subject Heat Transfer pt_BR
dc.rights Acesso Aberto pt_BR
dc.creator COSTA, Edson Guedes da.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Analysis of the performance of zinc oxide arresters. pt_BR
dc.identifier.citation COSTA, Edson Guedes da. Análise do desempenho de para-raios de óxido de zinco. 1999. 201f. (Tese de Doutorado em Engenharia Elétrica). Programa de Pós-Graduação em Engenharia Elétrica, Centro de Ciências e Tecnologia, Universidade Federal da Paraíba - Campus II - Campina Grande, 1999. pt_BR