dc.description.resumo |
Este trabalho apresenta uma análise paramétrica e sugere uma proposta para determinação
de reatâncias para reatores de neutro, utilizados como forma de mitigação da corrente de arco
secundário durante faltas monofásicas. Os parâmetros analisados foram o comprimento da li
nha de transmissão (LT), nível de compensação reativa shunt e relação entre capacitâncias de
sequência positiva e zero c1/c0. Para isso, uma análise de sensibilidade foi conduzida fazendo-se
uso do programa ATP (Alternative Transients Program) em um conjunto de 10 LTs. Os valo
res de corrente eficaz e pico da tensão de restabelecimento do arco secundário foram coletados
durante simulações de faltas monofásicas. Os dados foram utilizados para identificar a influên
cia devido à alteração dos parâmetros selecionados. O aumento do comprimento tornou as
correntes de arco secundário mais elevadas, sendo este efeito acentuado para os menores níveis
de compensação. A compensação reativa teve maior impacto na relação entre as reatâncias de
sequência positiva e zero considerada “ótima”, sendo este efeito mais notório nas LTs com uma
razão c1/c0 maior. Um procedimento de ajuste de curvas foi utilizado para obter equações que
representassem o conjunto de dados. Dois cenários foram considerados: os reatores de neutro
com menores reatâncias cujas correntes resultantes se encontravam abaixo de 50 A (reatores
“mínimos”) e os reatores cujas aplicações propiciaram os menores picos de tensão e correntes
eficazes, denominados reatores “ótimos”. As análises para o caso “ótimo” levaram a um conjunto
de equações que permitem a obtenção dos valores dos reatores de neutro para diferentes LTs
com base nas capacitâncias, não dependendo do comprimento da LT. As análises para o caso
“mínimo” mostraram-se mais complexas, e não foi possível identificar comportamentos entre
diferentes LTs que permitissem a formulação de um conjunto único de equações. Por fim, uma
metodologia foi proposta e comparada com resultados da literatura, permitindo o atendimento
aos critérios normativos para uma maior faixa de compensação reativa. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica. |
pt_BR |
dc.title |
Aprimoramento de técnicas de seleção de reatores de neutro em linhas de transmissão. |
pt_BR |
dc.date.issued |
2023-09-29 |
|
dc.description.abstract |
This paper presents a parametric analysis and suggests a proposal for determining reactan
ces for neutral reactors used to mitigate secondary arc current during single-phase faults. The
parameters analyzed were the length of the transmission line (TL), the level of reactive com
pensation shunt, and the ratio between positive and zero sequence capacitances c1/c0. To this
end, a sensitivity analysis was conducted using the program ATPDraw (Alternative Transients
Program) on a set of 10 TLs. The effective current and the first peak of the transient restoring
voltage (TRT) values were collected during simulations of single-phase faults. The data was
used to identify the influence of changing the selected parameters. Increasing the length made
the secondary arc currents higher, and this effect was more pronounced for the lower compen
sation levels. Reactive compensation had a greater impact on the ratio between the positive
and zero sequence reactances considered “optimal”, with this effect being more noticeable in
TLs with a higher c1/c0 ratio. A curve-fitting procedure was used to obtain equations that
represented the data set. Two scenarios were considered: the neutral reactors with the lowest
reactances whose resulting currents were below 50 A (“minimum” reactors) and those whose
applications provided the lowest TRT peaks and effective currents, called “optimal” reactors.
The analyses for the “optimal” case led to a set of equations that allow neutral reactor values
to be obtained for different TLs based on capacitances without depending on the length of the
TL. The analyses for the “minimum” case proved to be more complex, and it was not possible
to identify behaviors between different TLs that would allow a single set of equations to be
formulated. Finally, a methodology was proposed and compared with results in the literature,
allowing the normative criteria to be met for a wider range of reactive compensation. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/38822 |
|
dc.date.accessioned |
2024-11-01T20:24:16Z |
|
dc.date.available |
2024-11-01 |
|
dc.date.available |
2024-11-01T20:24:16Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Linhas de transmissão |
pt_BR |
dc.subject |
Sistemas elétricos |
pt_BR |
dc.subject |
Corrente de arco secundário |
pt_BR |
dc.subject |
Reator de neutro |
pt_BR |
dc.subject |
Transmission lines |
pt_BR |
dc.subject |
Electrical systems |
pt_BR |
dc.subject |
Secondary arc current |
pt_BR |
dc.subject |
Neutral reactor |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
BALBINO, Luan da Silva. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Improvement of techniques for selecting neutral reactors in transmission lines. |
pt_BR |
dc.identifier.citation |
BALBINO, Luan da Silva. Aprimoramento de técnicas de seleção de reatores de neutro em linhas de transmissão. 2024. 126 f. Dissertação (Mestrado em Engenharia Elétrica) – Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande, Paraíba, Brasil, 2023. |
pt_BR |