dc.description.resumo |
O presente trabalho tem como objetivo propor um metodologia para definir e calcular os
ganhos dos controladores de corrente e tensão das malhas internas de um conversor formador
de rede (CFR), garantindo a estabilidade do sistema em diferentes condições operacionais.
A metodologia para o projeto e validação da malha de controle de corrente e tensão é
baseada no modelo V que permite uma avaliação progressiva do controle desde a formulação
teórica até a implementação e verificação de desempenho. Como resultado, foi desenvolvidos
métodos para o projeto das malhas internas do conversor formadores de rede baseados nas
técnicas de sistema multivariáveis e por função de transferência. A análise dos resultados
mostrou que o método multivariável apresentou o melhor desempenho, destacando-se pela
sua maior estabilidade para diferentes cenários de teste. O método multivariável quando
analisado por degraus de potência ativo e reativo apresentou os melhores resultados, com
menor overshoot de 8.89% e tempo de acomodação de 0.015 s ao contrário dos métodos
por funções de transferência que atingiu um máximo overshoot durante a simulação de
36.46% e tempo de subida de 0.0495 s. Além disso, verificou-se que o método baseado em
funções de transferência, onde os termos de cruzamento foram considerados compensados,
teve um desempenho inferior ao ser submetido ao controle dVOC com oscilação nas curvas de
potência de até mais de 1 segundo durante as simulações, comprometendo a estabilidade do
sistema. E quando o CFR foi analisado conectado a uma carga que exige uma potência ativa
de 5000 W e reativa de 2000 V Ar todos os métodos foram capazes de entregar a potência
solicitada pela carga. Portanto, o método multivariável demonstrou ser a abordagem mais
robusta, proporcionando melhores resultados tanto na estratégia de controle por droop
quanto no dVOC e garantindo a estabilidade do CFR. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica |
pt_BR |
dc.title |
Modelagem e projeto dos controladores da malha interna de inversores formadores de rede |
pt_BR |
dc.date.issued |
2025-03-07 |
|
dc.description.abstract |
This work aims to propose a methodology to define and calculate the gains of the current
and voltage controllers of the internal loops of a grid-forming converter (CFR), ensuring
the stability of the system under different operating conditions. The methodology for the
design and validation of the current and voltage control loop is based on the V model
that allows a progressive evaluation of the control from the theoretical formulation to the
implementation and performance verification. As a result, methods were developed for the
design of the internal loops of the grid-forming converter based on the multivariable system
and transfer function techniques. The analysis of the results showed that the multivariable
method presented the best performance, standing out for its greater stability for different
test scenarios. The multivariable method when analyzed by active and reactive power steps
presented the best results, with a lower overshoot of 8.89% and settling time of 0.015 s unlike
the transfer function methods that reached a maximum overshoot during the simulation of
36.46% and rise time of 0.0495 s. Furthermore, it was found that the transfer function-based
method, where the crossover terms were considered compensated, had inferior performance
when subjected to dVOC control with oscillation in the power curves of up to more than
1 second during the simulations, compromising the stability of the system. And when the
CFR was analyzed connected to a load that requires an active power of 5000 W and a
reactive power of 2000 V Ar, all methods were able to deliver the power requested by the
load. Therefore, the multivariable method proved to be the most robust approach, providing
better results in both the droop control strategy and the dVOC and ensuring the stability
of the CFR. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/41608 |
|
dc.date.accessioned |
2025-04-22T13:21:02Z |
|
dc.date.available |
2025-04-22 |
|
dc.date.available |
2025-04-22T13:21:02Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Estabilidade |
pt_BR |
dc.subject |
Hardware in the loop |
pt_BR |
dc.subject |
Malhas internas |
pt_BR |
dc.subject |
Conversor formador de rede |
pt_BR |
dc.subject |
Stability |
pt_BR |
dc.subject |
Hardware in the loop |
pt_BR |
dc.subject |
Internal loop |
pt_BR |
dc.subject |
Network forming converter |
pt_BR |
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
OLIVEIRA, Alysson Hyago Pereira de. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
Invest Modeling and design of the internal mesh controllers of grid-forming inverters |
pt_BR |
dc.description.sponsorship |
CNPq |
pt_BR |
dc.description.sponsorship |
Capes |
pt_BR |
dc.identifier.citation |
OLIVEIRA, Alysson Hyago Pereira de. Modelagem e projeto dos controladores da malha interna de inversores formadores de rede. 2025. 93 f. Dissertação (Mestrado em Engenharia Elétrica) – Programa de Pós-Graduação em Engenharia Elétrica, Centro de Ciências e Tecnologia, Universidade Federal de Campina Grande, Paraíba, Brasil, 2025. |
pt_BR |