dc.description.resumo |
Esta dissertação avalia a coordenação de isolamento de três seccionadores, considerando surtos de impulsos de manobra para sistemas elétricos com tensões nominais acima de 300 kV e surtos de impulsos atmosféricos para tensões abaixo de 300 kV. A partir de ensaios de seccionadores isolados a ar, realizados em laboratórios de extra-alta tensão, são coletados dados para a verificação da coordenação de isolamento com distâncias diferentes de open-gap
e a distância de arco a seco no isolador, o que varia os valores de tensão disruptiva entre contatos e fase-terra, respectivamente. Uma análise estatística então é feita, com base nas curvas de distribuição normal de valores, tomando como base o método up and down com
valores de tensão de ruptura de cinquenta por cento das tensões de impulso (U50%) e a dispersão dos valores medidos ( ). Adicionalmente, uma análise minuciosa dos resultados nos revela as condições nas quais não se consegue garantir a coordenação de isolamento do seccionador. Com base nesta análise, propõem-se estudos laboratoriais mais detalhados e indica-se a necessidade de inclusão de ensaios de tipo que comprovem a coordenação de
isolamento do seccionador nos testes dielétricos das normas técnicas. |
pt_BR |
dc.publisher.country |
Brasil |
pt_BR |
dc.publisher.department |
Centro de Engenharia Elétrica e Informática - CEEI |
pt_BR |
dc.publisher.program |
PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA |
pt_BR |
dc.publisher.initials |
UFCG |
pt_BR |
dc.subject.cnpq |
Engenharia Elétrica |
|
dc.title |
Uma análise estatística da coordenação de isolamento em seccionadores de alta e extra-alta tensão. |
pt_BR |
dc.date.issued |
2015-05-13 |
|
dc.description.abstract |
This dissertation evaluates the insulation coordination of three disconnectors isolated by air, with respect to switching surges for electrical systems with rated voltages above 300 kV, and atmospheric surges for voltages below 300 kV. From assay disconnectors isolated by air, in extra-high-voltage laboratories, data is collected for checking insulation coordination on the electrical distances of "Open-Gap" and dry arc distance, on the insulator, which varies the breakdown voltage values between contacts and fase-to-ground, respectively. Then the
statistical analysis is performed on the normal distribution curve values, based on the method "up and down", on breakdown voltage values of the fifty percent of impulse voltages (U50%) and the dispersion of the measured values – standard deviation ( ). Thereafter, it is taken to
analyze the results, obtaining the conditions for which, it may ensure the insulation coordination of the disconnector. Based on this analysis, it is proposed to more detailed laboratory studies and indicates the inclusion of dielectric tests proving the insulation coordination of the disconnector in the type testing of the Brazilian technical standard. |
pt_BR |
dc.identifier.uri |
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9533 |
|
dc.date.accessioned |
2019-11-26T13:37:07Z |
|
dc.date.available |
2019-11-26 |
|
dc.date.available |
2019-11-26T13:37:07Z |
|
dc.type |
Dissertação |
pt_BR |
dc.subject |
Coordenação de Isolamento |
|
dc.subject |
Seccionadores |
|
dc.subject |
Ensaios de Tipo |
|
dc.subject |
Isolamento Elétrico |
|
dc.subject |
Suportabilidade a Impulso Atmosférico |
|
dc.subject |
Suportabilidade a Impulso de Manobra a Seco |
|
dc.subject |
Suportabilidade a Impulso de Manobra sob Chuva |
|
dc.subject |
Isolation Coordination |
|
dc.subject |
Disconnectors |
|
dc.subject |
Type Tests |
|
dc.subject |
Electrical Insulation |
|
dc.subject |
Support for Atmospheric Impulse |
|
dc.subject |
Support for Dry Maneuver Boost |
|
dc.subject |
Bearing Impulse Support in Rain |
|
dc.rights |
Acesso Aberto |
pt_BR |
dc.creator |
CAVALCANTE JÚNIOR, José Messias. |
|
dc.publisher |
Universidade Federal de Campina Grande |
pt_BR |
dc.language |
por |
pt_BR |
dc.title.alternative |
A statistical analysis of insulation coordination in high and extra high voltage disconnectors. |
pt_BR |
dc.identifier.citation |
CAVALCANTE JÚNIOR, José Messias. Uma análise estatística da coordenação de isolamento em seccionadores de alta e extra-alta tensão. 2015. 88f. (Dissertação) Mestrado em Engenharia Elétrica, Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande – Campina Grande - Paraíba - Brasil, 2015. |
pt_BR |