DSpace/Manakin Repository

Uma análise estatística da coordenação de isolamento em seccionadores de alta e extra-alta tensão.

Mostrar registro simples

dc.creator.ID CAVALCANTE JÚNIOR, J. M pt_BR
dc.creator.Lattes http://lattes.cnpq.br/3351376781364559 pt_BR
dc.contributor.advisor1 COSTA, Edson Guedes da.
dc.contributor.advisor1ID COSTA, E. G. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/3930289115658143 pt_BR
dc.contributor.advisor2 ASSIS, Francisco Marcos de.
dc.contributor.advisor2ID ASSIS, F. M. pt_BR
dc.contributor.advisor2Lattes http://lattes.cnpq.br/2368523362272656 pt_BR
dc.contributor.referee1 SOUZA, Benemar Alencar de.
dc.contributor.referee2 DANTAS, Karcius Marcellus Colaço.
dc.description.resumo Esta dissertação avalia a coordenação de isolamento de três seccionadores, considerando surtos de impulsos de manobra para sistemas elétricos com tensões nominais acima de 300 kV e surtos de impulsos atmosféricos para tensões abaixo de 300 kV. A partir de ensaios de seccionadores isolados a ar, realizados em laboratórios de extra-alta tensão, são coletados dados para a verificação da coordenação de isolamento com distâncias diferentes de open-gap e a distância de arco a seco no isolador, o que varia os valores de tensão disruptiva entre contatos e fase-terra, respectivamente. Uma análise estatística então é feita, com base nas curvas de distribuição normal de valores, tomando como base o método up and down com valores de tensão de ruptura de cinquenta por cento das tensões de impulso (U50%) e a dispersão dos valores medidos ( ). Adicionalmente, uma análise minuciosa dos resultados nos revela as condições nas quais não se consegue garantir a coordenação de isolamento do seccionador. Com base nesta análise, propõem-se estudos laboratoriais mais detalhados e indica-se a necessidade de inclusão de ensaios de tipo que comprovem a coordenação de isolamento do seccionador nos testes dielétricos das normas técnicas. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica
dc.title Uma análise estatística da coordenação de isolamento em seccionadores de alta e extra-alta tensão. pt_BR
dc.date.issued 2015-05-13
dc.description.abstract This dissertation evaluates the insulation coordination of three disconnectors isolated by air, with respect to switching surges for electrical systems with rated voltages above 300 kV, and atmospheric surges for voltages below 300 kV. From assay disconnectors isolated by air, in extra-high-voltage laboratories, data is collected for checking insulation coordination on the electrical distances of "Open-Gap" and dry arc distance, on the insulator, which varies the breakdown voltage values between contacts and fase-to-ground, respectively. Then the statistical analysis is performed on the normal distribution curve values, based on the method "up and down", on breakdown voltage values of the fifty percent of impulse voltages (U50%) and the dispersion of the measured values – standard deviation ( ). Thereafter, it is taken to analyze the results, obtaining the conditions for which, it may ensure the insulation coordination of the disconnector. Based on this analysis, it is proposed to more detailed laboratory studies and indicates the inclusion of dielectric tests proving the insulation coordination of the disconnector in the type testing of the Brazilian technical standard. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9533
dc.date.accessioned 2019-11-26T13:37:07Z
dc.date.available 2019-11-26
dc.date.available 2019-11-26T13:37:07Z
dc.type Dissertação pt_BR
dc.subject Coordenação de Isolamento
dc.subject Seccionadores
dc.subject Ensaios de Tipo
dc.subject Isolamento Elétrico
dc.subject Suportabilidade a Impulso Atmosférico
dc.subject Suportabilidade a Impulso de Manobra a Seco
dc.subject Suportabilidade a Impulso de Manobra sob Chuva
dc.subject Isolation Coordination
dc.subject Disconnectors
dc.subject Type Tests
dc.subject Electrical Insulation
dc.subject Support for Atmospheric Impulse
dc.subject Support for Dry Maneuver Boost
dc.subject Bearing Impulse Support in Rain
dc.rights Acesso Aberto pt_BR
dc.creator CAVALCANTE JÚNIOR, José Messias.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative A statistical analysis of insulation coordination in high and extra high voltage disconnectors. pt_BR
dc.identifier.citation CAVALCANTE JÚNIOR, José Messias. Uma análise estatística da coordenação de isolamento em seccionadores de alta e extra-alta tensão. 2015. 88f. (Dissertação) Mestrado em Engenharia Elétrica, Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande – Campina Grande - Paraíba - Brasil, 2015. pt_BR