DSpace/Manakin Repository

Avaliação de desempenho e risco em sistemas elétricos de potência.

Mostrar registro simples

dc.creator.ID SIQUEIRA, I. P. pt_BR
dc.creator.Lattes http://lattes.cnpq.br/6395538047388012 pt_BR
dc.contributor.advisor1 SOUZA, Benemar Alencar de.
dc.contributor.advisor1ID SOUZA, B. A. pt_BR
dc.contributor.advisor1Lattes http://lattes.cnpq.br/4987294390789975 pt_BR
dc.contributor.referee1 SCHILLING, Marcus Theodor.
dc.contributor.referee2 LYRA FILHO, Christiano.
dc.contributor.referee3 SILVA, Maria da Guia da.
dc.contributor.referee4 MOTA, Wellington Santos.
dc.contributor.referee5 NEVES, Washington Luiz Araújo.
dc.description.resumo Esta tese descreve um método formal de avaliar o desempenho e risco associados a sistemas elétricos de potência e instalações interligadas. O estudo propõe um modelo de propagação de perturbações e seus impactos nos valores esperados de indicadores de performance e risco de sistemas de potência, e sua contribuição e impacto cruzado de vários agentes e atores de mercado durante desligamentos no sistema elétrico. O método é baseado na propagação de perturbações em cascata através da topologia da rede elétrica, podendo ser usado para planejamento e diagnóstico de falhas em tempo real, e avaliação pós-operacional. Além das taxas de saída forçada e programada intrínsecas aos equipamentos, outros fatores são considerados tais como segurança e confiabilidade de proteções, falhas ocultas e de disjuntores, e tempos de restauração manual e religamento automático após uma perturbação. Sua contribuição conjunta determina o nível final de continuidade de cada nó da rede elétrica, e a fração de responsabilidade de cada agente. Com pequenas mudanças, o método pode ser aplicado a muitos outros processos industriais. Para isto, um programa em MatLab® foi desenvolvido para ser aplicável a qualquer processo que utilize componentes interdependentes. Um estudo de caso real ilustra sua aplicação a uma instalação elétrica de extra-alta tensão, enquanto um sistema de potência de pequena escala é usado ao longo da tese para ilustrar os métodos. pt_BR
dc.publisher.country Brasil pt_BR
dc.publisher.department Centro de Engenharia Elétrica e Informática - CEEI pt_BR
dc.publisher.program PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA pt_BR
dc.publisher.initials UFCG pt_BR
dc.subject.cnpq Engenharia Elétrica
dc.title Avaliação de desempenho e risco em sistemas elétricos de potência. pt_BR
dc.date.issued 2010-12-06
dc.description.abstract This thesis describes a formal method of assessing performance and risk associated with to electrical power systems and interconnected installations. The study proposes a disturbance propagation model and its impacts on the expected values ​​of performance and risk indicators of power systems, and their contribution and cross impact of various market players and actors during electrical system. The method is based on the propagation of cascade disturbances. through the topology of the power grid and can be used for planning and real-time fault diagnosis, and post-operative assessment. In addition to fees forced and programmed outputs intrinsic to the equipment, other factors are such as safety and reliability of protections, hidden failures and circuit breakers, and manual reset and automatic reclosure times after a disturbance. Your joint contribution determines the final level of continuity of each node of the power grid, and the fraction of responsibility of each agent. With small changes, the method can be applied to many other processes industrial For this, a MatLab® program has been developed to be applicable any process that uses interdependent components. A case study illustrates its application to an extra-high voltage electrical installation while a small scale power system is used throughout the thesis to illustrate the methods. pt_BR
dc.identifier.uri http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9562
dc.date.accessioned 2019-11-26T20:57:39Z
dc.date.available 2019-11-26
dc.date.available 2019-11-26T20:57:39Z
dc.type Tese pt_BR
dc.subject Confiabilidade
dc.subject Disponibilidade
dc.subject Desempenho
dc.subject Risco
dc.subject Modelagem de Falhas
dc.subject Programação de Falhas
dc.subject Desligamentos em Cascata
dc.subject Reliability
dc.subject Availability
dc.subject Performance
dc.subject Risk
dc.subject Failure Modeling
dc.subject Fault Scheduling
dc.subject Cascade Shutdowns
dc.rights Acesso Aberto pt_BR
dc.creator SIQUEIRA, Iony Patriota de.
dc.publisher Universidade Federal de Campina Grande pt_BR
dc.language por pt_BR
dc.title.alternative Performance and risk assessment in electrical power systems. pt_BR
dc.identifier.citation SIQUEIRA, Iony Patriota de. Avaliação de desempenho e risco em sistemas elétricos de potência. 2011. 560f. (Tese) Doutorado em Engenharia Elétrica, Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande – Campina Grande - Paraíba - Brasil, 2011. pt_BR